Dimensional Entry - FlowLine EchoWave LG11 Series Manual

Guided wave liquid level transmitter
Hide thumbs Also See for EchoWave LG11 Series:
Table of Contents

Advertisement

Appendix
Shape Selection Window: This window will shows the different tank shape options available in WebCal
Vertical Cylinder
Vertical Cylinder with Cone Bottom
Horizontal Cylinder with End caps
Horizontal Cylinder with Spherical Ends
Spherical
Rectangular
Strapping Table – Use this feature for manual entry
of measured tank distances and volumes.
Select any of the above tank shapes and press OK to
confirm.
C. DIMENSIONAL ENTRY
Dimensional Entry (Vertical Cylinder Example)
Choose the Sensor Output Units as Distance or Volume. After choosing the Sensor Output Units, select the
units of measurement in the pull down to the left.
Distance – Sensor Output Units (Vertical Cylinder Example)
Enter the dimensions of the tank. You must
enter data in all fields shown.
Sensor Height: Distance from the bottom of
the tank to the top of the threads.
Max. Fill Height: Distance from the bottom
of the tank to the operational full level of
liquid (20mA). This setting defines the
location of full current output and is the top of
the sensor's measurement range.
Min. Fill Height: Distance from the bottom of
the tank to the operational empty level of
liquid (4mA). This setting defines the location
of empty current output and is the bottom of the sensor's measurement range.
Probe Length: Distance of the probe from the bottom of the threads (feed through) to the end of the probe.
|
36
Units of Measurement
Distance
Volume
Inches
Cm
Gallons
Feet
Liters
Meters
Section Seven
®
.
MN300840 REV A5