STEP 5 – DIMENSIONAL ENTRY
Distance Mode (default): Output of sensor is based on the distance (height of liquid) in the tank. Any change
in liquid level will reflect linearly to the current output. The two values (Sensor Height and Fill-Height) below set
the 4-20 mA current span for the sensor. Both values will be set in the units shown under Height Units.
Height Units: Confirm units for use in Sensor Height and Fill-Height settings.
Sensor Height: Sets the location for 4mA. It is based on the distance from the Empty level position
(bottom of tank) to the Measurement location for the sensor (bottom of sensor).
Fill-Height: Sets the location for 20mA. It is based on the distance from the Empty level position
(bottom of tank) to the Full level position (see below).

STEP 6 - TANK LEVEL CONFIRMATION

Verify the Height Units, Sensor Height & Fill-Height. All values were calculated and set in the previous
Dimensional Entry window. Make any adjustments if required.
QS310140 Rev A2