HARDWARE INSTALLATION

These versatile UPS systems can be mounted in a rackmount or vertical /tower orientation. This versatility is
especially important to growing organizations with changing needs that value having the option to position
a UPS on the floor or in the rackmount system. Please follow the instructions below for the respective
mounting methods.
RACKMOUNT INSTALLATION: RACKMOUNT EARS INSTALLATION
Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the
mounting brackets.
Step 1: Remove the dust covers
Remove ten dust covers from the screw holes as shown below.
Step 2: Rackmount ear & hanging bracket installation
Attach two rackmount ears to the UPS using the provided flat head screws M5X7L*8pcs and tighten two
hanging brackets with the pan head screws M5X6L*6pcs.
1
2
Step 3: Rackmount rail Installation
The rails adjust to mount in 19 in (48 cm) racks from 20.5 in to 36 in (52 cm to 91.5 cm) deep. Select the
proper holes in the rack for positioning the UPS in the rack. The UPS uses 3 rack units, rack holes positions 1
through 9.
Position the guide screws on the rails into the rear rack square holes to temporarily support the rails in
place. Tighten the front rail screws on the rack.
Step 4: Adjust rackmount rails to fit your rack
Adjust the rails depth to match your rack depth. Secure the rackmount rails to your rack using pan head
screws M5X6L*4pcs and plastic washers *4pcs at the front of the rack. (Located in position 4 & position 8)
Secure the rails to the rear of the rack using pan head screws M5X6L*4pcs and plastic washers *4pcs.
9
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.