CyberPower OL6KRTMB Installation And Operation Manual page 34

Smart app online ups system
Table of Contents

Advertisement

USING THE UPS SYSTEM CONT.
LCD Setting Configuration Cont.
CONFIGURE
SUBMENU
Language
Generator Mode
2
Communication
Dry Relay Set
Converter Mode
3
Screen Saver
Clear Event Log
Button OFF LOCK
Charger Function
AVAILABLE SETTINGS
[English] [Español-Spanish] [Français-French]
[Deutsch-German]
User can select the desired LCD control panel language.
[Disable] [Enable]
When the UPS input power source is a generator set
the UPS will operate normally without transferring to
Battery Mode when this is [Enable].
[Disable] [Enable]
All communication ports on the UPS are
[Disable] or [Enable].
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
Sets UPS events and convert to real potential-free
Dry Contacts for industrial control.
[Converter O ] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Sets [O/P Freq = 50Hz] or [O/P Freq = 60Hz] to
convert the input frequency to required output
frequency.
[Disable] [1 Minutes] [5 Minutes]
Sets the amount of time the LCD screen stays on after
no user input. The [Disable] option keeps the LCD
screen on at all times.
[Activate?]
Clears all the events stored in the LCD Control Panel
Event Log.
[Disable] [Enable]
When [Enable] is set the Power ON/OFF Button is
locked and will not function to prevent accidental UPS
power ON/OFF operation.
[SBM] [Constant]
Sets [SBM] to activate the Smart Battery Management
to charge the batteries.
Sets [Constant] to use trickle charge method to
charge the batteries.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
DEFAULT SETTING
English
Disable
Enable
I/P Power Fail
Converter OFF
5 minutes
None
Disable
SBM
28