USING THE UPS SYSTEM CONT.
LCD Setting Configuration Cont.
CONFIGURE
SUBMENU
Language
Generator Mode
2
Communication
Dry Relay Set
Converter Mode
3
Screen Saver
Clear Event Log
Button OFF LOCK
Charger Function
AVAILABLE SETTINGS
[English] [Español-Spanish] [Français-French]
[Deutsch-German]
User can select the desired LCD control panel language.
[Disable] [Enable]
When the UPS input power source is a generator set
the UPS will operate normally without transferring to
Battery Mode when this is [Enable].
[Disable] [Enable]
All communication ports on the UPS are
[Disable] or [Enable].
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
Sets UPS events and convert to real potential-free
Dry Contacts for industrial control.
[Converter O ] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Sets [O/P Freq = 50Hz] or [O/P Freq = 60Hz] to
convert the input frequency to required output
frequency.
[Disable] [1 Minutes] [5 Minutes]
Sets the amount of time the LCD screen stays on after
no user input. The [Disable] option keeps the LCD
screen on at all times.
[Activate?]
Clears all the events stored in the LCD Control Panel
Event Log.
[Disable] [Enable]
When [Enable] is set the Power ON/OFF Button is
locked and will not function to prevent accidental UPS
power ON/OFF operation.
[SBM] [Constant]
Sets [SBM] to activate the Smart Battery Management
to charge the batteries.
Sets [Constant] to use trickle charge method to
charge the batteries.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
DEFAULT SETTING
English
Disable
Enable
I/P Power Fail
Converter OFF
5 minutes
None
Disable
SBM
28