CyberPower OL6KRTMB Installation And Operation Manual page 41

Smart app online ups system
Table of Contents

Advertisement

TECHNICAL SPECIFICATIONS
MODELS
CONFIGURATION
Capacity (VA)
Capacity (Watts)
Form Factor
Energy-saving
Technology
INPUT
Input Voltage Range
Input Frequency Range
Input Power Factor
Cold Start
OUTPUT
Output Waveform
Output Voltage
Output Frequency
Transfer Time (Typical)
Rated Power Factor
Harmonic Distortion
Crest Factor
ECO Mode Bypass
Voltage Range
Outlets for the
Maintenance Bypass
Module with Outlets
Outlets for the
Maintenance Bypass
Module without Outlets
PROTECTION
Surge Protection
Phone / Network Surge
Protection
Overload Protection
Short Circuit Protection
BATTERY
Specifications
Recharge Time 0-90%
(Typical)
OL6KRTMB
OL6KRTHW
6000 VA
6000 W
Rackmount/Tower
ECO Mode E ciency> 96%
200~240 V
40~70 Hz (auto-sensing)
0.99
Yes
Sine wave
200, 208, 220, 230, 240 V ±2% (Configurable)
50/60 Hz ±0.25 Hz (Auto-Sensing or Configurable)
0ms
1
THD < 3% at Linear Load, < 5% at Non-linear Load
3 : 1
±10%, ±15% (Configurable)
(2) L6-20R, (4) L6-30R, (1) Hard Wire 3-wire
(1) Hard Wire 3-wire
IEC 61000-4-5 Level 3 (2430 Joules)
RJ11/RJ45 (One In/One Out)
Line Mode: 105~125% Load for 1 min, 126~150% Load for 10 sec
Battery Mode: 105~130% Load for 10 sec, 131~150% Load for 2 sec
UPS Output Cut o Immediately or Input Fuse / Circuit Breaker Protection
(20) 12 V/7 Ah
4 hours
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
OL8KRTMB
OL8KRTHW
8000 VA
8000 W
(20) 12 V/9 Ah
5 hours
OL10KRTMB
OL10KRTHW
10000 VA
10000 W
ECO Mode E ciency> 97%
35