Attaching External Indicators; Connection Procedure - Omron Sti F3SJ-A Series User Manual

Safety light curtain
Hide thumbs Also See for Sti F3SJ-A Series:
Table of Contents

Advertisement

Wiring/Installation

Attaching External Indicators

An external indicator can be connected and turned ON based on the operation of the F3SJ. Indicators can be
attached to emitters and/or receivers.
Example:
• Indicate that the F3SJ is in lockout
• Indicate that a machine is stopped (safety output is OFF)
• Indicate that the F3SJ is in muting or override
Do not use the auxiliary output or external indicator output for safety applications.
Human body may not be detected when F3SJ fails, resulting in serious injury.

Connection Procedure

1.
Remove the cap from the side (emitter or receiver) to which you want to attach the external indicator.
(driver comes with F39-A01P -PAC, F39-JJ3N)
2.
Attach the external indicator.
Recommended items
Name
External indicator set
Universal indicator cable
- When attaching a cable or cap, tightly fasten the screws (M2, in 4 places, recommended torque: 0.15N m). Failure to
do so may cause the cable/cap to come loose, leading to deterioration of the protective functions.
F3SJ-A
126
User's Manual
Muting lamp (external indicator)
External indicator set
Model F39-A01P
-PAC
2. 2.
Cap
(Case color : Black)
1. 1.
Model name
F39-A01P -PAC
A set consisting of an LED indicator, connection cable, and mounting
brackets.
The LED indicator is available in red, green, or yellow.
F39-JJ3N
Available external indicators
- Incandescent lamp: 24VDC, 3 to 7W
- LED lamp: Load current 300mA max.
Commercially
available
indicator
Universal indicator
3.
cable
Model F39-JJ3N
Brown: +, Blue: -
Description
1.