Installation
34
The following steps must be followed when installing the DACT module:
1. Remove all power (AC and DC) from FACP before proceeding with installation
2. Remove the Keypad/Display from the main circuit board as described in the
beginning of this section
3. Insert the supplied plastic snap-in standoff into mounting hole located at the
bottom center of the DACT-UD module (insert into back of board)
4. Carefully plug connector J1 on back of the DACT-UD module into connector J2
on the MS-9600 main circuit board, being careful not to bend any pins and at the
same time, insert plastic snap-in standoff into mounting hole in main board
5. Align the mounting holes in the DACT module with the premounted standoffs on
the FACP main circuit board
Figure 2.12 DACT J1 Connector to FACP J2 Connector
6. Secure the module to the standoffs on the main circuit board with the three
screws supplied with the DACT-UD. It is important that the supplied screws be
used to secure the module to the metal standoff in order to help protect against
electrical transients.
Figure 2.13 DACT Installation on Standoffs
7. Reinstall Keypad/Display on the main circuit board by positioning the unit over
the appropriate standoffs and securing with screws which were loosened in step 2
8. Make certain to program the control panel for DACT operation
Optional Modules and Devices
Standoff
Standoff
Standoff
J2
Standoff (snap-in)
J1 Connector located on
back of DACT module
MS-9600 PN 51335:E1 2/14/08
J1
Mounting Screw
Mounting Screws
Snap-in Standoff