Relays - Honeywell Fire-Lite Alarms MS-9600 Manual

Fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9600:
Table of Contents

Advertisement

Master Programming Level
SYSTEM SETUP
1=TIMERS
2=NAC

3=RELAYS

System Setup Screen #2
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
Relay Screen #2
MS-9600 PN 51335:E1 2/14/08
3.6.5.6 Relays
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to
configure two of the three main circuit board Form-C relays. The following screen
will be displayed:
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
To program Relay 1 or Relay 3, press the number corresponding to the selected
relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no
effect on its programming. The following screen will appear for each relay to be
programmed:
1=TYPE
Relay Type Screen
Pressing 1 for Type while viewing the Relay Screen will cause the following
screens to be displayed:
While viewing the selected screen, press the number corresponding to the desired
relay type to program the main circuit board relay. The choice will be stored in
memory and the display will return to the Relay Type Screen which will show the
programmed type choice. Press the Escape key to return to the Relays Selection
Screen and repeat the preceding procedure for the remaining relays.
Note: AR in SUPERVISORY AR and PROCMON AR indicates AutoResettable
which means that the relay will not latch when either of these conditions occur. If
the corresponding condition is cleared, the relay will return to its normal state
without the necessity of resetting the control panel.
RELAYS
RELAY #
ALARM
RELAY
1=PROCMON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
RELAY
1=MEDICAL
Relay Screen #4
Programming
93