Programming
PROGRAMMING
1=POINT PROGRAM
2=HISTORY

3=PROGRAM CHECK

Maintenance Screen #1
106
3.7.3 Program Check
Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be
displayed:
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONE NO OUTPUT
The Program Check feature allows the programmer to view the zones which have been
programmed to the Notification Appliance Circuits on the control panel but have not
been programmed to Initiating Devices as well as other circuits with no input or output
correlations. Pressing 1 while viewing Program Check screen will cause a screen
similar to the following to be displayed.
NACS NO INPUT
NAC 1
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55
and 67 but no input devices have been programmed to any of these zones. Use the up
and down arrow keys to view all the NAC zones without input assignments for NAC1,
NAC2, NAC3 and NAC4.
Note: If the NACs have been configured for Class A in the Setup option, only NAC1 and
NAC2 will display test information. NAC 3 and NAC 4 will display asterisks (*) and
will not be included in the test.
Pressing 2 while viewing the Program Check screen will display a screen similar to the
following:
ZONES NO INPUT
05 07 09 10 11 1M001
The Zone No Input screen allows the programmer to view the zones which have not
been programmed to at least one input device (not including general alarm Zone 00).
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have
been programmed to an addressable module (control module in this example) with an
address of 001 on loop 1 but have not been programmed to any input devices. Use the
up and down arrow keys to view all the zones without input assignments.
Maintenance Programming Level
PROGRAM CHECK
Program Check Screen
25 31 44 55 67