NFPA Standard-Specific Requirements
The following figure illustrates an example of Central Station/Remote Station Reporting using a
411UD. The relay contacts from the MS-9600 may be used to trip any dialer UL listed for Central
Station/Remote Station Reporting Services.
Note: The Monitor Module input, which is being used to
monitor the 411UD Relay #2 Output (programmed for
DACT Trouble), must be programmed as 'Trouble' at
Fire•Lite MS-9600.
24 VDC nonresettable power
*If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules.
152
Channel 4 (2.2K EOL)
Monitor Module EOL resistor
Relay Output (DACT Trouble)
24 VDC nonresettable power
MS-9600
Supervisory Relay
MS-9600
Trouble Relay
MS-9600
Alarm Relay
(2.2K EOLS
P/N 27070)
_
+
Fire•Lite MS-9600
Figure C.3 Fire•Lite MS-9600 Connection to 411UD
Alarm
Trouble
Supervisory
Table C.2 411-UD Connections to MS-9600
1
Channel1
2
3
Channel 2
4
5
Channel 3
6
7
8
1
2
3
4
5
6
7
8
Monitor
Module
Circuit
Input
1 2 3 4 5 6 7 8 9
411UD
MS-9600
TB2-1
TB5-1
TB2-2
TB5-3
TB2-3
TB5-5
TB2-4
TB5-6
TB2-5
TB5-7
TB2-6
TB5-9
MS-9600 PN 51335:E1 2/14/08
Correlations
411UD
J4 Not Installed
*
SLC Loop