Programming
See Page
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
See Page
54
To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until
the display reads PAS Yes. Each press of the 2 key will cause the display to toggle
between PAS Yes and PAS No. Refer to "Positive Alarm Sequence" on page 120.
For example, if a detector with address 005 is to be configured for PAS operation:
Select PAS Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this
example Z001
Program an output, such as a control module that is to be activated by detector
005 by assigning the same zone to it; in this example Z001
Program an output, such as a control module, for PAS activation by assigning
zone Z97 to it. This control module may be connected to a signaling device
used to indicate a PAS condition (do not use a Notification Appliance Circuit
for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay
timer to some value
With the preceding program settings, when the detector with address 005 is
activated, zone Z97 will cause its associated control module to activate
immediately, sounding the connected PAS signaling device. Following the PAS
delay time, zone Z001 will cause its associated control module to activate and the
control panel will initiate an alarm condition.
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a
preprogrammed time delay of up to three minutes while allowing for visual
verification by a person. Note that the alarm relay and communicator will respond
to the initial alarm immediately. In addition, Zone 98 will activate. This zone can
be programmed to a control module which may be used to activate a sounder or
indicator which the installer designates as a Presignal indication (do not use a
Notification Appliance Circuit for this purpose). To enable the Pre-signal feature,
press 3 while viewing Edit Detector Screen #3 until the display reads Pre-signal
Yes. Each press of the 3 key will cause the display to toggle between Pre-signal Yes
and Pre-signal No. Refer to "Presignal" on page 119.
For example, if a detector with address 005 is to be configured for Pre-Signal
operation:
Select Pre-signal Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this
example Z001
Program an output, such as a control module that is to be activated by detector
005 by assigning the same zone to it; in this example Z001
Program an output, such as a control module, for Pre-signal activation by
assigning zone Z98 to it. This control module may be connected to a signaling
device used to indicate a Pre-signal condition (do not use a Notification
Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre-
signal delay timer to some value
With the preceding program settings, when the detector with address 005 is
activated, zone Z98 will cause its associated control module to activate
immediately, sounding the connected signaling device to indicate the Pre-signal
condition. Following the Pre-signal delay time, zone Z001 will cause its associated
control module to activate and the control panel will initiate an alarm condition.
Master Programming Level
MS-9600 PN 51335:E1 2/14/08