Programming
TIMER
1=PAS DELAY
000
2=PRE SIGNAL
000
3=WATERFLOW
000
Timer Screen #1
86
3.6.5.4.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-
signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press
2 while viewing Timer Screen #1. The following screen will be displayed:

PRESIGNAL DELAY

RANGE 0-180 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay
time consisting of three digits, such as 009 for nine seconds. Upon entering the
third digit, the time delay will be stored in the control panel memory and the display
will return to the Delay Screen which will indicate the new delay time.
Note that the FACP can be programmed for either PAS or Pre-signal operation, not
both. For this reason, if the PAS Delay timer is set with a value greater than 000
and then the Pre-Signal Delay timer is set with a value greater than 000, the PAS
Delay timer will be automatically reset to 000. Only one of the two timers can have
a delay time set for it.

3.6.5.4.3 Waterflow Delay

A delay can be added prior to declaring a waterflow type of alarm. Be careful to
include any built-in delays of the waterflow device. The factory default setting for
Waterflow delay is 000 for no delay. To select a Waterflow delay of 01 to 90
seconds for all devices programmed for Waterflow delay, press 3 while viewing
Timer Screen #1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay
time consisting of two digits, such as 25 for twenty-five seconds. Upon entering the
second digit, the time delay will be stored in the control panel memory and the
display will return to the Delay Screen which will indicate the new delay time.
Pre-signal Delay Screen
Waterflow Delay Screen
Master Programming Level
MS-9600 PN 51335:E1 2/14/08