Outdoor Fan Pcb Abnormality - Daikin VRV X RXQ6-48ANR Series Service Manual

Cooling only 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

5.34 Outdoor Fan PCB Abnormality

Applicable
All outdoor unit models
Models
H7
Error Code
Method of Error
Detect according to values detected with current sensor.
Detection
Error Decision
When the current sensor is abnormal.
Conditions
Supposed
 Disconnection/Short circuit in fan motor leads or disconnection of connector
Causes
 Defective fan PCB (A4P, A7P)
Troubleshooting
210
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check for fan motor applicable to the error code H7 while in monitor mode.
• Sub code
Fan PCB (A7P): H07-21 (Master), H7-23 (Slave 1), H7-25 (Slave 2)
Fan PCB (A4P): H07-22 (Master), H7-24 (Slave 1), H7-26 (Slave 2)
Turn OFF the power supply
and wait for 10 minutes.
Is
resistance
between Vcc-UVW
and between GND-UVW
of the fan motor lead
in balance?
NO
YES
SiME341909EA
Replace the defective fan motor.
Replace the defective fan PCB.
RXQ6/8AR: A4P
RXQ10-16AR: A4P, A7P
Part 6 Service Diagnosis

Hide quick links: