Daikin VRV X RXQ6-48ANR Series Service Manual page 103

Cooling only 50/60 hz
Table of Contents

Advertisement

SiME341909EA
1.4.15 Compensating the Floor Temperature (Cooling)
(For units with the infrared presence/floor sensor)
Offset the detected value of the infrared presence/floor sensor with a certain temperature. This
setting should be used to have the actual floor temperature detected when, for example, the unit
is installed close to a wall.
12 (22)
Specific usages of this setting
There is no problem with the standard setting in the usual condition. Change the setting in the
cases indicated in the following table.
-The unit is installed close to a wall or a
window.
-High thermal capacity of the floor (such as
concrete, etc).
-There are many heat sources including PC.
-There is a non-negligible heat source such as
floor heating.
Note(s)
This setting is available only in cooling operation.
1.4.16 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to 01 at
the factory.
 FXFSQ25-80AR
Mode
 FXFSQ100-140AR
Mode
Note(s)
1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
Part 5 Field Settings and Test Operation
Mode
First
Second
No.
Code No.
Code No.
01
02
11
03
04
Environment
First
Second
No.
Code No.
Code No.
01
13
0
(23)
02
03
First
Second
No.
Code No.
Code No.
01
13
0
(23)
02
03
(2), initial setting by remote controller is required.
Operation
Mode
Insufficient cooling
Cooling
Excessive cooling
Contents
All round
outlet
Lower
Standard
than
2.7 m
High
Lower than
Lower than
Ceiling(1)
3.0 m
High
Lower than
Lower than
Ceiling(2)
3.5 m
Contents
All round
outlet
Lower
Standard
than
3.2 m
High
Lower than
Lower than
Ceiling(1)
3.6 m
High
Lower than
Lower than
Ceiling(2)
4.2 m
Field Settings for Indoor Unit
: Factory setting
Contents
4°C
2°C
0°C
–2°C
Problem
Contents
–2°C
2°C or 4°C
: Factory setting
Ceiling Height
4-way
3-way
Outlets
Outlets
Lower
Lower than
Lower than
than
3.0 m
3.1 m
Lower than
Lower than
3.4 m
3.3 m
Lower than
4.0 m
3.5 m
: Factory setting
Ceiling Height
4-way
3-way
Outlets
Outlets
Lower
Lower than
Lower than
than
3.6 m
3.4 m
Lower than
Lower than
3.9 m
4.0 m
Lower than
4.5 m
4.2 m
2-way
Outlets
3.5 m
3.8 m
2-way
Outlets
4.2 m
4.2 m
97