Daikin VRV X RXQ6-48ANR Series Service Manual page 159

Cooling only 50/60 hz
Table of Contents

Advertisement

SiME341909EA
Error code
Defective subcooling heat exchanger outlet thermistor
J9 - 01
(Master)
Defective subcooling heat exchanger outlet thermistor
J9 - 02
(Slave 1)
Defective subcooling heat exchanger outlet thermistor
J9 - 03
(Slave 2)
Error detection of subcooling heat exchanger outlet
J9 - 08
pipe thermistor (Master)
Error detection of subcooling heat exchanger outlet
J9 - 09
pipe thermistor (Slave 1)
Error detection of subcooling heat exchanger outlet
J9 - 10
pipe thermistor (Slave 2)
JA - 06
Defective high pressure sensor: Open (Master)
JA - 07
Defective high pressure sensor: Short (Master)
JA - 08
Defective high pressure sensor: Open (Slave 1)
JA - 09
Defective high pressure sensor: Short (Slave 1)
JA - 10
Defective high pressure sensor: Open (Slave 2)
JA - 11
Defective high pressure sensor: Short (Slave 2)
JC - 06
Defective low pressure sensor: Open (Master)
JC - 07
Defective low pressure sensor: Short (Master)
JC - 08
Defective low pressure sensor: Open (Slave 1)
JC - 09
Defective low pressure sensor: Short (Slave 1)
JC - 10
Defective low pressure sensor: Open (Slave 2)
JC - 11
Defective low pressure sensor: Short (Slave 2)
L1 - 01
IPM error: Compressor M1C (Master)
L1 - 02
Defective current sensor: Compressor M1C (Master)
L1 - 03
Current offset: Compressor M1C (Master)
L1 - 04
IGBT error: Compressor M1C (Master)
L1 - 05
Jumper settings error: Compressor M1C (Master)
L1 - 07
IPM error: Compressor M1C (Slave 1)
L1 - 08
Defective current sensor: Compressor M1C (Slave 1)
L1 - 09
Current offset: Compressor M1C (Slave 1)
L1 - 10
IGBT error: Compressor M1C (Slave 1)
L1 - 11
IPM error: Compressor M1C (Slave 2)
L1 - 12
Defective current sensor: Compressor M1C (Slave 2)
L1 - 13
Current offset: Compressor M1C (Slave 2)
L1 - 14
IGBT error: Compressor M1C (Slave 2)
L1 - 15
Jumper settings error: Compressor M1C (Slave 1)
L1 - 16
Jumper settings error: Compressor M1C (Slave 2)
L1 - 17
IPM error: Compressor M2C (Master)
L1 - 18
Defective current sensor: Compressor M2C (Master)
L1 - 19
Current offset: Compressor M2C (Master)
L1 - 20
IGBT error: Compressor M2C (Master)
L1 - 21
Jumper settings error: Compressor M2C (Master)
L1 - 22
IPM error: Compressor M2C (Slave 1)
L1 - 23
Defective current sensor: Compressor M2C (Slave 1)
L1 - 24
Current offset: Compressor M2C (Slave 1)
L1 - 25
IGBT error: Compressor M2C (Slave 1)
L1 - 26
Jumper settings error: Compressor M2C (Slave 1)
L1 - 36
EEPROM abnormality: Compressor M1C (Master)
L1 - 37
EEPROM abnormality: Compressor M2C (Master)
L1 - 38
EEPROM abnormality: Compressor M1C (Slave 1)
L1 - 39
EEPROM abnormality: Compressor M2C (Slave 1)
L1 - 40
EEPROM abnormality: Compressor M1C (Slave 2)
L1 - 41
EEPROM abnormality: Compressor M2C (Slave 2)
Part 6 Service Diagnosis
Description of error
Troubleshooting
Refer to the J9 flowchart and make a diagnosis
of the relevant thermistor based
on the Error code shown to the left.
Refer to the JA flowchart and make a diagnosis
of the relevant sensor based
on the Error code shown to the left.
Refer to the JC flowchart and make a diagnosis
of the relevant sensor based
on the Error code shown to the left.
The inverter PCB may be defective or a PCB other than
the specified is mounted.
Refer to the L1 flowchart and make a diagnosis based
on the Error code shown to the left.
Troubleshooting by Error Code
Diagnosis
153

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents