Daikin VRV X RXQ6-48ANR Series Service Manual page 102

Cooling only 50/60 hz
Table of Contents

Advertisement

Field Settings for Indoor Unit
1.4.12 Thermostat Differential Changeover
Set when remote sensor is to be used.
Differential value during thermostat ON/OFF control can be changed.
Mode
12 (22)
1.4.13 Auto Restart after Power Failure
Mode
12 (22)
When the "Auto Restart after Power Failure" setting is turned OFF, all the units will remain OFF
after power failure, or after the main power supply is restored. When this setting is turned ON
(factory setting), the units that were operating before the power failure will automatically restart
operation after power failure, or after the main power supply is restored.
Due to the aforementioned, when the "Auto restart after power failure" setting is ON, be careful
for the following situations that may occur.
1. The air conditioner will start operation suddenly after power failure,
Caution
2. During maintenance, if the main power supply is turned OFF while the
1.4.14 Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to "LL airflow" when cooling thermostat is OFF.
12 (22)
96
First
Second
No.
Code No.
Code No.
01
2
02
First
Second
No.
Code No.
Code No.
01
5
02
or when the main power supply is restored. The user might be surprised
and wonder why the air conditioner turned ON suddenly.
units are in operation, the units will automatically start operation
(the fan will rotate) after the power supply is restored due to completion
of the maintenance work.
Mode
First Code
Second
No.
No.
Code No.
01
6
02
SiME341909EA
: Factory setting
Contents
1ºC
0.5ºC
: Factory setting
Contents
OFF
ON
: Factory setting
Contents
LL tap
Set fan speed
Part 5 Field Settings and Test Operation