Setting For Brc4M Series - Daikin VRV X RXQ6-48ANR Series Service Manual

Cooling only 50/60 hz
Table of Contents

Advertisement

SiME341909EA
4.2

Setting for BRC4M Series

The address for the wireless remote controller is set to 1 at the factory. To change the setting,
proceed as follows:
1. Hold down the FILTER SIGN RESET button and the INSPECTION button for at least 4
2. Press the SELECT button and select a multiple setting (A/b). Each time the button is
3. Press the TEMP buttons to set the address.
4. When the RESERVE button is pressed, the setting is confirmed and the usual display
Part 3 Remote Controller
seconds to get the Field Setting mode.
(Indicated in the display area in the figure.)
pressed the display switches between A and b.
Address can be set from 1 to 6, but set it to 1-3 and to same address as the receiver. (The
receiver does not work with address 4-6.)
returns.
Address
Multiple setting
Address Setting for Wireless Remote Controller
4
1
3
2
45