Daikin VRV X RXQ6-48ANR Series Service Manual page 106

Cooling only 50/60 hz
Table of Contents

Advertisement

Field Settings for Indoor Unit
1.4.22 Setting of Swing Patterns when Cooling Thermostat is OFF
In cooling operation, when the airflow direction is set to swing, flaps swing even when the
thermostat is OFF. This setting allows to change the airflow direction when the thermostat is
OFF.
Mode
13 (23)
1.4.23 Setting of Circulation Airflow
This is to set whether the circulation airflow function is enabled or disabled.
Mode
13 (23)
1.4.24 Circulation Airflow Patterns
This setting is to change the appearance pattern of the circulation airflow direction depending
on the installation environment of the indoor unit.
Cooling
1.4.25 Switching Panel Type
 FXFSQ-AR
Change this setting depending on the type of the panel connected.
13 (23)
100
First
Second
No.
Code No.
Code No.
01
02
03
7
04
05
06
07
First
Second
No.
Code No.
Code No.
01
13
02
Movement pattern
01: Pattern 1
Appearance
Time
02: Pattern 2
(seconds)
03: Pattern 3
13 (23)-14
04: Pattern 4
Indicates the horizontal flap is in the position of reducing airflow volume (where the flap is
reversed).
Mode
First
Second
No.
Code No.
Code No.
01
15
02
Fixed
Set Position
Set Position
P0
Set Position
Set Position
P2
Set Position
Contents
Disabled
Enabled
(a)
(b)
120
600
120
600
0
0
120
600
Contents
Standard panel
Designer panel
Part 5 Field Settings and Test Operation
SiME341909EA
: Factory setting
Swing
Swing
P0
P0
Swing
P2
P2
Swing
: Factory setting
: Factory setting
(c)
(d)
120
600
0
0
120
600
120
600
: Factory setting