Daikin VRV X RXQ6-48ANR Series Service Manual page 244

Cooling only 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code
Reference
CHECK 4 Refer to page 264.
238
A
The insulation
resistance of the fan
motor is not more
than 1 MΩ.
NO
CHECK 4
Is the power
transistor normal?
YES
Connect and disconnect the
connectors as shown in the
table.
The
inverter PCB (#1)
has damage.
NO
Turn ON the power supply,
and then press the ON button.
The
system enters
standby mode before the
outdoor fan starts
rotating.
NO
The
system enters
standby mode before
completing the startup
operation of the
compressor.
NO
The error U2 recurs.
NO
YES
NO
RXQ6-12AR
A1P
A3P
A1P
X20A
X4A
X20A
X28A
X6A
X28A
X40A
X63A
X40A
X41A
YES
YES
YES
YES
SiME341909EA
Replace the fan motor.
If the motor gets severely
damaged, the inverter
PCB (#1) should also be
replaced.
#1
RXQ6/8AR: A4P
RXQ10-16AR: A4P, A7P
Replace the inverter PCB.
(1)
RXQ14/16AR
A3P
A6P
X4A
X6A
X63A
X63A
X41A
X4A
X61A
X6A
Replace the inverter PCB
(#1).
If the inverter PCB gets
severely damaged, the
compressor and the fan
motor may have been
damaged.
Replace the inverter PCB
(#1).
Replace the inverter PCB
(#1).
If the inverter PCB gets
severely damaged, check
for the compressor.
Check for wirings.
Continue operation.
The error could have
resulted from causes such
as instantaneous power
failure.
Part 6 Service Diagnosis