Settings By Bs Buttons - Daikin VRV X RXQ6-48ANR Series Service Manual

Cooling only 50/60 hz
Table of Contents

Advertisement

Field Settings for Outdoor Unit
2.3

Settings by BS Buttons

The following settings can be made using the BS buttons on the PCB.
In case of a multi outdoor system, make these settings with the master outdoor unit (settings
made with a slave unit are disabled).
BS buttons
MODE
Used to make
setting mode
changes.
 Normal mode:
 Setting mode: Used to make changes to operating status, performance settings or address
 Monitor mode: Used to verify contents of settings, quantity of units, current value of some
 Mode changing procedure can be selected using the MODE (BS1) button as shown
108
BS1
BS2
BS3
SET
RETURN
(TEST)
(RESET)
Used to make
field settings.
 Blank: If no abnormality is detected and initialization of communication was completed.
 Flashing combination of letter and number (4 digits): Error code detected by outdoor
control or trouble by communication.
setting.
parameters during operation of outdoor unit.
below:
Press and hold the
MODE (BS1) button
for 5 seconds or more
Setting mode
Press the MODE
SEG1 SEG2 SEG3
(BS1) button once
7 segment display (SEG1-3)
Normal mode
Setting mode
Monitor mode
Press the MODE
(BS1) button once
Normal mode
SEG1 SEG2 SEG3
Part 5 Field Settings and Test Operation
SiME341909EA
SEG1 SEG2 SEG3
Monitor mode
SEG1 SEG2 SEG3