Daikin VRV X RXQ6-48ANR Series Service Manual page 253

Cooling only 50/60 hz
Table of Contents

Advertisement

SiME341909EA
Part 6 Service Diagnosis
Diagnosis Flowchart-3
U7-03
Error code
Sub code
(Transmission error between master
and slave 1)
The
multi transmission
wirings to multi slave 1 have
caused wiring disconnection in
them or are being
disconnected.
YES
Diagnosis Flowchart-4
U7-04
Error code
Sub code
(Transmission error between master
and slave 2)
The
multi transmission
wirings to multi slave 2
have caused wiring disconnection in
them or are being
disconnected.
YES
Diagnosis Flowchart-5
U7-05
Error code
Sub code
(Multi system error)
Multi outdoor unit
system?
YES
NO
NO
NO
Troubleshooting by Error Code
Replace the outdoor unit main
PCB (A1P) for multi slave 1.
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P) for multi slave 2.
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P).
Disconnect the outdoor unit multi
transmission wirings, and then
reset the power supply.
247