Table 5: ACH580 Parameters
MD5 Parameters
#
Name
GROUP 96 - SYSTEM
96.04 MACRO SELECT
GROUP 99 - MOTOR DATA
99.06 MOTOR NOM CURR
99.07 MOTOR NOM VOLT
99.09 MOTOR NOM SPEED
99.10 MOTOR NOM POWER
GROUP 12 - STANDARD AI
12.15 AI1 UNIT SELECTION
12.19 AI1 SCALED ATAI1 MIN
12.20 AI1 SCALED AT AI1 MAX
12.25 AI2 UNIT SELECTION
12.29 AI2 SCALED AT AI2 MIN
12.30 AI2 SCALED AT AI2 MAX
GROUP 20 - START/STOP/DIR
20.01 EXT1 COMMANDS
20.21 DIRECTION
20.41 START INTERLOCK 1
20.42 START INTERLOCK 2
GROUP 22 - REFERENCE SELECT
22.11 EXT SPEED REF1
22.22 CONSTANT SPEED SEL1
22.41 SPEED REF SAFE
GROUP 28 - FREQUENCY REFERENCE CHAIN
28.11 EXT1 FREQUENCY REF1
28.22 CONSTANT FREQ SEL1
28.41 FREQUENCY REF SAFE
28.72 FREQ ACCELERATION TIME 1
28.73 FREQ DECELERATION TIME 1
GROUP 31 - FAULT FUNCTIONS
31.01 External Event 1 Source
31.14 NUMBER OF TRIALS
31.16 DELAY TIME
31.27 STALL FREQUENCY LIMIT
31.25 AR OVERCURRENT
GROUP 46 - MONITOR / SCALING SETTINGS
46.02 FREQUENCY SCALING
GROUP 58 - EMBEDDED FILEDBUS
58.01 PROTOCOL ENABLE
58.03 NODE ADDRESS
58.04 BAUD RATE
58.05 PARITY
58.14 COMMUNICATION LOSS ACTION
58.15 COMMUNICATION LOSS MODE
58.16 COMMUNICATION LOSS TIME
58.33 ADDRESSING MODE
58.06 Communication Control
GROUP 71 - EXTERNAL PID1
71.32 GAIN
71.33 INTEGRATION TIME
GROUP 97 - MOTOR CONTROL
97.20 U/F RATIO
www.DaikinApplied.com
Unit
VALUE
HVAC DEFAULT
A
Motor Specific
V
Motor Specific
Motor Specific
RPM
HP
Motor Specific
MA
200
1000
MA
200
1000
EMBEDDED FIELDBUS
FORWARD
NOT USED
NOT USED
EFB REF1
ALWAYS OFF
RPM
0
EFB REF1
ALWAYS OFF
Hz
0
S
60
S
60
DI2
5
S
3
Hz
45
ENABLE
1000
MODBUS RTU
1 (SAF) or 2 (RF/EF)
19.2 KBPS
8 NONE 2
SPEED REF SAFE
CW/REF1/REF2
S
25.0 S
MODE0
Enabled
1.00
S
2155
LINEAR
33
Appendix