Fluorescent Wiring Information - Lutron Electronics GRAFIK Eye GRX-4000 Series Installation, Operation And Maintenance Manual

Dimming panel
Hide thumbs Also See for GRAFIK Eye GRX-4000 Series:
Table of Contents

Advertisement

Fluorescent Wiring
Information
Ballast and Fixture Wiring
One Lamp
SWITCHED HOT - BLACK
TO DIMMING
DIMMED HOT - ORANGE
PANEL
TO NEXT BALLAST
Two Lamps
SWITCHED HOT - BLACK
TO DIMMING
DIMMED HOT - ORANGE
PANEL
TO NEXT BALLAST
Two Compact Fluorescent Lamps
SWITCHED HOT - BLACK
TO DIMMING
DIMMED HOT - ORANGE
PANEL
TO NEXT BALLAST
Three Lamps
SWITCHED HOT - BLACK
TO DIMMING
DIMMED HOT - ORANGE
PANEL
TO NEXT BALLAST
Notes:
Ballasts must be located so that the maximum case temperature
is less than 75 °C (167 °F) and the relative humidity is less than
90%, non-condensing.
Avoid situations where strong air drafts blow directly on bare
bulbs (minimum start temperature is 10 °C).
Good metal-to-metal contact between lamp pins and lamp holder
contacts is necessary for proper dimming performance. Knife-
edge sockets are recommended.
For those who purchased Start Up with their Lutron Dimming
System - you may want to stop here and have the Lutron Field
Engineer set-up the system. Please call for a Start Up visit at
least 10 working days before your requested date.
34
Reference Sheets for GRAFIK Eye Dimming Panel
Hi-lume FDB/
Eco-10 BALLAST
NEUTRAL - WHITE
Mount to
Grounded Fixture
Hi-lume FDB/
Eco-10 BALLAST
NEUTRAL - WHITE
Mount to
Grounded Fixture
Hi-lume FDB/
Eco-10 BALLAST
NEUTRAL - WHITE
Mount to
Grounded Fixture
Hi-lume FDB/
Eco-10 BALLAST
NEUTRAL - WHITE
Mount to
Grounded Fixture
RED
LAMP
BLUE
RED
LAMP
YELLOW
LAMP
BLUE
RED
RED
YELLOW
YELLOW
BLUE
BLUE
RED
LAMP
YELLOW
LAMP
BLUE/WHITE
BLUE
LAMP
Compact Fluorescent lamps must be 4 pin.
Ballast cases and fixtures must be earth grounded.
Yellow and blue w/white trace leads, from the ballast should be
kept as short as possible.
Ballasts are not designed for remote mounting. Total length of
wire from the ballast to the lamp socket is not to exceed 7 ft.
(2.1 m) for T8, T12, and not to exceed 3 ft. (0.9 m) for T4, T5.
240V Ballasts have different wire colors-follow the label on each
individual ballast.