6-Phase/12 Pulse Input 400 V Class Drive Models CIMR-A 4T0208 to 0675

Item
CIMR-A 4T
Maximum Applicable
Motor Capacity kW (HP)
Input Current (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Input Power (kVA)
Rated Output Capacity
(kVA)
<3>
Rated Output Current
(A)
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
conditions, and power supply impedance. This input current rating is the 3-Phase total input current rating. For the 6-Phase input current rating
see
Table
C.1.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Table A.2 Power Ratings (CIMR-A 4T0208 to 0675)
0250
132
ND Rating
(200)
<1>
110
HD Rating
(150)
ND Rating
228
<2>
HD Rating
190
ND Rating
227
HD Rating
189
ND Rating
191
<4>
HD Rating
165
ND Rating
250
<4>
HD Rating
216
User-adjustable between 1 kHz and 10 kHz
0296
0362
160
185
(250)
(300)
132
160
(200)
(250)
275
317
228
275
6-Phase/12-Pulse: 380 Vac to 480 Vac 50/60 Hz
Note: 6-Phase isolated supply with each of the output windings phase shifted
by 30 electrical degrees or Hybrid 6-Phase topology.
274
316
227
274
226
276
198
232
<5>
<5>
296
362
260
304
<5>
<5>
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Three-phase: 380 V to 480 V (proportional to input voltage)
400 Hz (user-adjustable)
A.1 Power Ratings
Specification
0414
0515
220
250
(350)
(400)
185
220
(300)
(350)
376
427
317
376
-15% to 10%
±5%
375
425
316
375
316
392
282
343
<5>
<4>
414
515
370
450
<5>
<4>
User-adjustable between 1 kHz and 5 kHz
0675
355
(500-550)
315
(400-450-500)
603
511
601
534
514
461
<4>
<4>
675
605
<4>
<4>
53