Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL
Listed closed-loop crimp terminals when wiring the drive main circuit terminals. Use only the tools recommended by the
terminal manufacturer for crimping. Refer to
terminal recommendations.
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of UL Listed
crimp terminals when wiring the drive main circuit terminals. Use only crimping tools as specified by the crimp terminal
manufacturer. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent) for the insulation cap.
Table C.2
matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and
insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size
for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
The closed-loop crimp terminal sizes and values listed in
for proper selections.
Terminal
Wire Gauge
Screws
14 AWG
M4
M4
M5
12 / 10 AWG
M6
M8
M4
8 AWG
M5
M8
M4
M5
6 AWG
M6
M8
M10
M6
4 AWG
M8
M10
M6
3 / 2 / 1 AWG
M8
M10
M8
1/0 AWG
1/0 AWG × 2P
M10
1 AWG × 2P
M10
2 AWG × 2P
2/0 AWG
M10
2/0 AWG × 2P
3/0 AWG
M10
M10
3/0 AWG × 2P
3/0 AWG × 4P
M12
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Closed-Loop Crimp Terminal Size on page 65
Table C.2
Table C.2 Closed-Loop Crimp Terminal Size
Crimp Terminal
Model Number
Machine No.
R2-4
YA-4
R5.5-4
YA-4
R5.5-5
YA-4
R5.5-6
YA-4
R5.5-8
YA-4
8-4
YA-4
R8-5
YA-4
R8-8
YA-4
14-NK4
YA-4, YA-5
R14-5
YA-4, YA-5
R14-6
YA-4, YA-5
R14-8
YA-4, YA-5
R14-10
YA-4, YA-5
R22-6
YA-5
R22-8
YA-5
R22-10
YA-5
38-S6
YA-5
R38-8
YA-5
R38-10
YA-5
YA-5
R60-8
YF-1, YET-300-1
YA-5
R60-10
YF-1, YET-300-1
YA-5
38-L10
YF-1, YET-150-1
70-10
YF-1, YET-300-1
80-10
YF-1, YET-300-1
YF-1, YET-150-1
80-L10
YF-1, YET-300-1
YF-1, YET-150-1
80-L12
YF-1, YET-300-1
are Yaskawa recommendations. Refer to local codes
Tool
Insulation
Die Jaw
Model No.
AD-900
AD-900
AD-900
AD-900
AD-900
AD-901
AD-901
AD-901
AD-902, AD-952
AD-902, AD-952
AD-902, AD-952
AD-902, AD-952
AD-902, AD-952
AD-953
AD-953
AD-953
AD-954
AD-954
AD-954
AD-955
TD-321, TD-311
AD-955
TD-321, TD-311
AD-954
TD-224, TD-212
TD-323, TD-312
TD-323, TD-312
TD-227, TD-214
TD-323, TD-312
TD-227, TD-214
TD-323, TD-312
C.1 UL Standards
for closed-loop crimp
Cap
Code
<1>
TP-003
100-054-028
TP-005
100-054-029
TP-005
100-054-030
TP-005
100-068-029
TP-005
100-068-030
TP-008
100-054-031
TP-008
100-054-032
TP-008
100-061-111
TP-014
100-054-033
TP-014
100-054-034
TP-014
100-051-261
TP-014
100-054-035
TP-014
100-061-112
TP-022
100-051-262
TP-022
100-051-263
TP-022
100-061-113
TP-038
100-068-031
TP-038
100-051-264
TP-038
100-061-114
TP-060
100-051-265
TP-060
100-051-266
TP-038
100-051-556
TP-080
100-054-036
TP-080
100-051-267
TP-080
100-051-557
TP-080
100-051-558
65