baltur TBL 18 Instruction Manual For Installation, Use And Maintenance page 59

Single-stage diesel burners
Table of Contents

Advertisement

Available languages

Available languages

IRREGULARITY
Defective flame with sparks.
Flame not properly shaped with presence of
smoke and soot.
Defective flame, flickering or protruding from
combustion orifice.
Corrosion inside the boiler.
Soot at chimney outlet.
POSSIBLE CAUSE
1 Spraying pressure is too low.
2 Too much combustion air.
3 Nozzle inefficient because dirty or
worn.
4 Water in the fuel.
1 Insufficient combustion air flow.
2 Nozzle inefficient because dirty or worn.
3 Nozzle capacity too low with respect to
combustion chamber volume.
4 Combustion chamber unsuitably
designed or too small.
5 Unsuitable refractory coating (it reduces
excessively the space of the flame).
6 Boiler or chimney ducts blocked.
7 Spraying pressure is low.
1 Excessive draught, only when there is
an extractor in the chimney.
2 Nozzle inefficient because dirty or worn.
3 Water in the fuel.
4 Dirty flame disk.
5 Too much combustion air.
6 Air passage between flame disk and
diffuser excessively closed.
1 Boiler operating temperature too low
(below the dew point).
2 Smoke temperature too low,
approximately below 130 °C for diesel.
1 Excessive cooling of smoke
(approximately below 130°C) in the
chimney, for an outside chimney not
adequately heat insulated or cold air
infiltration.
27 / 30
0006160431_202112
REMEDY
1 Restore it at the required value.
2 Reduce combustion air
3 Clean or replace.
4 Drain water from the tank using a
suitable pump. Never use the burner
pump for this purpose.
1 Increase combustion air.
2 Clean or replace.
3 Decrease diesel flow rate to suit the
chamber (thermal power will obviously
be lower than necessary) or replace the
boiler.
4 Increase nozzle flow by replacing it.
5 Modify it, carefully abiding by
the instructions given by boiler
manufacturer.
6 Arrange for cleaning.
7 Restore it at the required value.
1 Adjust the suction fan speed by
changing the pulley diameter.
2 Clean or replace.
3 Drain water from the tank using a
suitable pump. Never use the burner
pump for this purpose.
4 Clean.
5 Reduce combustion air.
6 Correct the position of the combustion
head regulating device.
1 Increase the operating temperature.
2 Increase diesel flow rate is the boiler
allows it.
1 Improve insulation and close any
opening letting cold air into the chimney.
ENGLISH

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Tbl 26Tbl 353556001035680010

Table of Contents