CONTROL AND COMMAND EQUIPMENT LMO...

OPERATION.
The reset button «EK...» is the main element to access all diagnostics functions (activation
and deactivation) and serves to unlock the command and control device.
The multi-coloured «LED» indicates the command and control device status during both
operation and diagnostics functions.
Both «LED» and «EK...» are positioned under the transparent button. Pressing this button, you reset the command and control equipment.
There are two diagnostics choices:
1. Visual indication directly on the reset button: operation and diagnostics of device status.
2. Diagnostics with interface: in this case the OCI400 connecting cable is necessary and it can be connected to a PC with ACS400 software, or
to gas analysers of different manufacturers.
VISUAL INDICATION.
During operation, the command and control equipment phase is indicated on the reset button. The table lists all colour sequences and their
meaning. To activate the diagnostics function, hold the reset button down for at least 3 seconds. A quick red flashing indicates that the function
is active. Likewise, hold the reset button down for at least 3 seconds to deactivate the function (the switching will be indicated with a flashing
yellow light).
Condition
Waiting time, other intermediate conditions
Fuel oil preheating "ON", max waiting time 5 s. (tw)
Ignition phase
Correct operation, current strength of flame detector above
the minimum allowed
Incorrect operation, current strength of flame detector below
the minimum allowed value
Decrease in power supply voltage
Burner shut down condition
Fault indication (see colour key)
Extraneous light upon burner start-up
Quick flashing for diagnostics
NO LIGHT.
RED.
Operating position
Diagnostics
Colour code table
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
YELLOW.
GREEN.
0006160431_202112
Operating position
PC interface / diagnostic
analyser
> 3 s
EK
Colour sequence
. . . . . . . .
. . . . . . . . . Fixed
23 / 30
RED
YELLOW
GREEN
Colours
No light
Yellow continuous
Intermittent yellow
Green
Intermittent green
Alternating Yellow and Red
Red
Intermittent red
Alternating Green and Red
Quick flashing red