Ferroli OMNIA S HYBRID H 3.2 Installation, Use & Maintenance Manual page 78

Indoor wall unit for split reversible hybrid heat pumps which can be combined with an outdoor dhw heater
Table of Contents

Advertisement

Fault
Fault
code
Overtemperature protec-
F09
tion triggered
F10
Delivery sensor fault
F11
Return sensor fault
A11
Gas valve connection
F12
DHW sensor fault
F13
Fumes probe fault
"Fumes evacuation pope
A14
safety device triggered"
"Supply voltage lower than
F34
180V"
"Power supply frequency
F35
incorrect"
A23-
A24-
A26-F20
Pressure sensor fault
F21-
F40-
F47-F51
System water pressure
F37
incorrect
F39
External probe fault
F19
Board parameter fault
F50 -
Thermostat limit fault with
F53
parameter b06 = 1 or 4
Maximum number of con-
F64
secutive resets exceeded
F62
Calibration request
Combustion control or gas
A88
valve specific errors
78
EN
Possible cause
Delivery sensor damaged
"No water circulation in the system"
Air in the system
Sensor damaged
Wiring short-circuited
Wiring interrupted
Sensor damaged
Wiring short-circuited
Wiring interrupted
"Damage to the electrical connection between the
control unit and gas valve"
Sensor damaged
Wiring short-circuited
Wiring interrupted
Probe damaged
Wiring short-circuited
Wiring interrupted
"A07 fault generated 3 times in the last 24 hour"
Problems with the mains electricity
Problems with the mains electricity
"Parameter configured incorrectly"
"System pressure problems (transducer)"
b06 set to 3
Pressure too low
Pressure transducer not connected or damaged
Probe damaged or wiring short-circuited
"Probe disconnected after activating sliding tem-
perature"
"Incorrect setting of board parameter"
"No/poor water circulation in the system"
Air in the system
Incorrect parameter
Maximum number of consecutive resets exceeded
"New board or boiler not yet calibrated"
"Calibration activated with burner lit.
Combustion problem, gas valve or electronic board
faulty"
Cod. 3542B230 - Rev. 00 - 02/2022
OMNIA S HYBRID H 3.2
Remedy
"Check the correct position and operation of the delivery sensor and replace
it, if necessary"
"Check the circulator and heating system"
Bleed the system
Check the wiring or replace the sensor
Check the wiring or replace the sensor
check the wiring or replace the valve
Check the wiring or replace the sensor
Check the wiring or replace the fumes probe
See fault A07
Check the electrical system
Check the electrical system
"Check if parameter b04 is configure correctly"
System pressure value outside the set limits (transducer)
Load the system
Check the pressure transducer
Check the wiring or replace the sensor
Reconnect the external probe or disable the sliding temperature"
"Check and change parameter b15 to 3, if necessary"
"Check the circulator and heating system"
Bleed the system
Check the correct parameter setting
"Disconnect the power supply to the boiler for 60 seconds and then, reset the
boiler"
"Run the calibration procedure [AUTO SETUP]."
"Reset the fault and run the calibration procedure [AUTO SETUP]". Replace
the gas valve or the electronic board, if necessary."