Connection Of System Add-Ons; How To Access The Heat Pump Hydronic Board - Ferroli OMNIA S HYBRID H 3.2 Installation, Use & Maintenance Manual

Indoor wall unit for split reversible hybrid heat pumps which can be combined with an outdoor dhw heater
Table of Contents

Advertisement

OMNIA S HYBRID H 3.2
Method C - setting for thermostat temperature control from two zones
The request may come, for example, from the two room thermostats of the two
system zones to be served. The system will operate in the mode set by the user
interface.
Set par. 6.1 = 3 (mode set).
Set par. 5.3 = 1 (enabling control of 2 zones)
H-L1
L1-C
Operating status
(TZ1 - zone 1)
(TZ2 - zone 2)
Serving zone 1 through the activation of
Closed
Open
pump P_o
Serving zone 2 through the activation of
pump P_c and temperature control sent with
Open
Closed
mixing valve SV3 (if installed) and water
temperature probe Tw2 (if installed)
Serving zone 1 through the activation of
pump P_o and serving zone 2 through the
activation of pump P_c and temperature
Closed
Closed
control sent with mixing valve SV3 (if in-
stalled) and water temperature probe Tw2
(if installed)
Open
Open
Off zone 1 and zone 2

7.9.2 Connection of system add-ons

The unit can manage system add-ons, such as an external circulation pump / zone 1 water pump, zone 2 water pump, 3-way mixer valve for zone 2, 3-way diverter
valve for hot/cold mode, DHW recirculation pump, electric heating element for DHW boiler, thermal solar pump, photovoltaic input and smart grid. All these elements
are controlled by the heat pump hydronic board.

7.9.3 How to access the heat pump hydronic board

Remove the front panel (see "7.9.1 Opening the front panel"
on page 42)
The board (detail A "fig. 33 - heat pump hydronic board") is
located inside the heat pump electric box (see "fig. 8 - View
without front panel" on page 25). To access it, you need
to remove the sheet metal cover by removing the fastening
screws.
TZ1
TZ2
NOTE
The wiring of the thermostat should correspond to the settings of the user
interface.
A
fig. 33 - heat pump hydronic board
Cod. 3542B230 - Rev. 00 - 02/2022
fig. 32 - Method C thermostat ( 2 zones)
B
E
P
Q
E
H
L1
C
43