Use Of Flexible Hose Pipe Ø50 And Ø60 - Ferroli OMNIA S HYBRID H 3.2 Installation, Use & Maintenance Manual

Indoor wall unit for split reversible hybrid heat pumps which can be combined with an outdoor dhw heater
Table of Contents

Advertisement

7.7.4 Use of flexible hose pipe Ø50 and Ø60
The calculation shown in the tables below includes the starter accessories with code 041087X0 for Ø50 and code 041050X0 for Ø60.
Flexible hose pipe
A maximum of 4 metres of flue Ø80 mm can be used between the boiler and the tract to the reduced diameter (Ø50 o Ø60), and a maximum of 4 metres of flue Ø80
mm on the extraction (with the maximum flue length with Ø50 and Ø60) see "fig. 23 - Diagram for pipe installation with flexible pipes only" on page 38.
A =
Ø50 - 22 m MAX
Ø60 - 60 m MAX
Follow the indications shown below to use this diameter.
Enter the TSP parameter menu and change the value of the P68 parameter to the value of the length of the flue used. After changing the value, perform the calibration
procedure (see "11.2.5 Checking the boiler combustion values" on page 69).
SC04
13
12
10
8
6
4
2
0
0
38
EN
max 4 m
Ø80
fig. 23 - Diagram for pipe installation with flexible pipes only
10
20
fig. 24 - Graph for choice of flue parameter
Cod. 3542B230 - Rev. 00 - 02/2022
OMNIA S HYBRID H 3.2
max 4 m
Ø80
30
40
m
50
60