Commissioning
32
9.1.1

As-delivered state

If no customized settings were ordered:
• Assign PV parameter Level limit detection (8/16 mA mode)
• MAX safety mode
• Alarm condition set to min. 3.6 mA
• DIP switch for locking in OFF position
• Bluetooth switched on
• Density range > 0.7 g/cm³
• Switching times 0.5 s when the fork is covered and 1.0 s when it is uncovered
• HART burst mode switched off
9.2

Function check

Before commissioning the measuring point, check whether the post-mounting and post-
connection checks have been performed:
 Checklist in "Post-mounting check" section
A
 Checklist in "Post-connection check" section
A
9.3

Switching on the device

All configuration tools provide a commissioning assistant that supports the user when
setting the most important configuration parameters (Guidance menu
Commissioning wizard).
9.4
Establishing a connection via FieldCare and
DeviceCare
9.4.1

Via HART protocol

2
3
1
 23
Options for remote operation via HART protocol
1
PLC (programmable logic controller)
2
Transmitter power supply unit, e.g. RN221N (with communication resistor)
3
Connection for Commubox FXA195 and Field Communicator 375, 475
4
Handheld terminal
5
Computer with operating tool (e.g. FieldCare/DeviceCare, AMS Device Manager, SIMATIC PDM)
6
Commubox FXA195 (USB)
7
Field Xpert SMT70
8
VIATOR Bluetooth modem with connecting cable
9
Device
6
4
5
Liquiphant FTL64 HART
9
8
7
Endress+Hauser
A0046562