Commissioning
34
Click "Settings" and select the desired language:
Setting the language for the local display via DeviceCare
Navigation: System → Display → Language
Set the desired language in the Language parameter.
9.7

Device configuration

9.7.1
Commissioning with DIP switch and operating keys on the
electronic insert
 24
Operating keys and DIP switches on the 4 to 20 mA HART electronic insert
1
Operating key for reset password (for Bluetooth login and Maintenance user role)
1+2 Operating keys for device reset (as-delivered state)
2
Operating key for Proof test (> 3 s)
3
DIP switch for safety function, software-defined (SW, default=MAX) or set permanently to MIN
4
DIP switch for locking and unlocking the device
Setting the MIN or MAX safety mode via the DIP switch
• When the switch is set to "SW", the MIN or MAX setting is defined by the software, with
MAX being the default value.
• In the "MIN" switch position, the setting is permanently MIN irrespective of the software.
Display
4
3
Liquiphant FTL64 HART
A0046404
A0046406
1
2
A0046573