Wiring; Wiring Precautions - Mitsubishi Electric MELSECQ Series User Manual

Multichannel high-speed counter module
Hide thumbs Also See for MELSECQ Series:
Table of Contents

Advertisement

4
PROCEDURES AND SETTINGS BEFORE
OPERATION
4.4
4.4.1
Downloaded from
ManualsNet.com

Wiring

This section describes wiring an encoder and controller to the QD63P6.

Wiring precautions

One of the conditions to maximize the QD63P6 functions and make the system high-
reliable, the external wiring has to be laid so that the QD63P6 becomes less subject to
noise.
This section describes the precautions on external wiring.
(1) Inputting a signal of different voltage may result in a malfunction or
mechanical failure.
(2) For 1-phase input, always perform pulse input wiring on the phase A
side.
(3) When pulse status noise is input, the QD63P6 may miscount.
(4) Take the following measures against noise for high-speed pulse input.
(a) Always use a shielded twisted pair cable and provide grounding.
(b) Wire the shielded twisted pair cables so as not to be in parallel with wires causing
much noise such as power lines or I/O wires while keeping a distance of at least
150 mm (5.91 inch) between such wires. Also install the shielded twisted pair
cables as short as possible.