3
SPECIFICATIONS
3.3.2
Device
No.
Programmable controller
X00
Module READY
X01
CH1
X06
CH2
X0B
CH3
X10
CH4
X15
CH5
X1A
CH6
Downloaded from
ManualsNet.com

Functions of I/O signals

The following table shows the I/O signals of the QD63P6.
I/O numbers (X/Y) and buffer memory addresses in Description describe only for channel
1.
For I/O numbers (X/Y) and buffer memory addresses from channels 2 to 6, refer to Section
3.3.1 and Section 3.4.1.
(1) I/O signals
Signal name
QD63P6
CPU
•Turns ON at reset or power-ON of the programmable controller CPU when counting
of the QD63P6 is ready, and the count processing is performed.
•Turns OFF when watchdog timer error or an error which affects the system (error
code: 810 to 850) occurs.
•The count processing is not performed when the module READY (X00) is OFF.
•This signal is used for an interlock of sequence programs.
•Turns ON when the present value A (Un\G10 and 11)/present value B (Un\G200 and
201)
•Turns OFF when the present value A (Un\G10 and 11)/present value B (Un\G200 and
201)
•For details of the general operation, refer to Section 5.3.
Coincidence detection
point setting
(Un\G6 and 7)
Counter value large
Present value A
(Un\G10 and 11)
Counter value large
(X01)
Counter value
coincidence
(X02)
Counter value small
(X03)
Coincidence signal
reset command
(Y01)
search engine
Table 3.5 I/O signals
In preparation
Status of the QD63P6
Module READY
(X00)
Coincidence detection point setting (Un\G6 and 7).
Coincidence detection point setting (Un\G6 and 7).
Immediately after power-ON or reset
of the programmable controller CPU
0
0
1
ON
OFF
ON
t*
3.3 I/O Signals to the Programmable Controller CPU
Description
Performed by the QD63P6.
Performed by the sequence program.
Watchdog timer error or
Ready
an error which affects the system
ON
OFF
Performed by the QD63P6.
Performed by the sequence program.
100
98
99
100
OFF
ON
OFF
ON
OFF
OFF
* t
2ms
3.3.2 Functions of I/O signals
1
2
3
4
5
6
101
102
7
ON
OFF
ON
8
OFF
t*
3