READING EXAMPLE
Example of MODBUS RTU command for reading the temperature (float value) T = 24.270019 °C from the register 0x19:
Device EE210; slave ID 242 [F2 in Hex]
Reference document, chapter 6.3: http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b.pdf
Request [Hex]: F2 03 00 19 00 02 01 0F
Modbus ID
address
Request
F2
[Hex]:
Response [Hex]: F2 03 04 29 00 41 C2 80 A1
Modbus ID
Function
address
code
Response
F2
03
[Hex]:
For decoding of float values (stored according standard IEEE754), please refer to AN0103, chapter 7.
Example of decoding:
Response [Hex]:
Byte 1
Byte 2
(Register 2 - Hi)
(Register 2 – Lo)
41
C2

TECHNICAL DATA

(Modification rights reserved)

Measured Values

Relative Humidity (RH)
Working range
RH accuracy
(incl. hysteresis, non-linearity and repeatability)
1)
Type T1 (wall), T2 (duct):
-15...40 °C
-15...40 °C
-40...60 °C
Type T3 (remote):
at 20 °C
(68 °F)
Type T13 (outdoor):
-15...40 °C
(5...104 °F)
-15...40 °C
-40...60 °C
Temperature (T)
T accuracy
Type T1, T2
± ∆T [°C]
Type T13
± ∆T [°C]
1) Traceable to intern. standards, administrated by NIST, PTB, BEV,... The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times
standard deviation). The accuracy was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
For Type T13: at 24 V DC and RL=250 for A6 versions.
6
Function
Starting
Starting
code
address Hi
address Lo
03
00
19
Register 1
Byte count
value Hi
04
29
Byte 3
(Register 1 - Hi)
29
0...100 %RH
≤90 %RH
(5...104 °F)
>90 %RH
(5...104 °F)
(-40...140 °F)
≤90 %RH
≥90 %RH
(5...104 °F)
(0...140 °F)
No. of
No. of
register Hi
register Lo
00
02
Register 1
Register 2
Register 2
value Lo
value Hi
value Lo
00
41
C2
Byte 4
(Register 1 - Lo)
00
±(1.3 + 0.003*measured value) %RH
±2.3 %RH
±(1.5 + 0.015*measured value) %RH
±2.5 %RH
±(1.6 + 0.005*measured value) %RH
±3 %RH
±(2.3 + 0.008*measured value) %RH
Type T3
± ∆T [°C]
T [°C]
T [°C]
CRC
01
0F
CRC
80
A1
Value in decimal
24,270019
T [°C]