If any of the indicators are amber, or if the power supply status indicator does not light,
replace the power supply.
Ensure the power supply on/off switch is in the "O" off position.
1.
Disconnect the power cord tie strap from the power cord, and unplug the power cord from
2.
the power supply.
Remove the power supply unit by grasping the power supply handle, push the release
3.
button [1], and slide the power supply out of the chassis [2] as shown in the following
figure.
Oracle Database Appliance X9-2-HA Storage Shelf Hot Pluggable Components
Description
AC power fail indicator
Fan fail indicator
Power supply status indicator
DC power fail indicator
Release lever
AC connector
On/Off switch
Chapter 3
3-13