The network wizard and the product setup can be carried out independently of
each other. A network connection is required for the Solar.web installation wiz-
ard.
Configuring the
1
Fronius Smart
Meter TS as the
primary meter
2
3
4
5
6
7
8
The Fronius Smart Meter TS is configured as a primary meter.
Configuring the
1
Fronius Smart
Meter TS as a
secondary meter
2
3
4
5
6
7
8
9
10
11
38
Establish a connection to the inverter (LAN1) with a network cable (CAT5
STP or higher).
Open the access point by touching the sensor once
flashes blue.
In the browser address bar, enter and confirm IP address 169.254.0.180. The
installation wizard is opened.
Follow the installation wizard in the individual sections and complete the in-
stallation.
Add system components in Solar.web and start up the PV system.
Access the inverter website.
-
Open the web browser.
-
In the address bar of the browser, enter the IP address (IP address for
WLAN: 192.168.250.181, IP address for LAN: 169.254.0.180) or the host
and domain name of the inverter and confirm.
-
The inverter website is displayed.
Click the "Device configuration" button.
Log in to the login area with the "Technician" user and the technician pass-
word.
Access the "Components" menu area.
Click the "Add component" button.
In the "Position" drop-down list, set the position of the meter (feed-in point
or consumption point). For more information on the position of the Fronius
Smart Meter TS, see
Positioning
Click the "Add" button.
Click the "Save" button to save the settings.
Access the inverter website.
-
Open the web browser.
-
In the address bar of the browser, enter the IP address (IP address for
WLAN: 192.168.250.181, IP address for LAN: 169.254.0.180) or the host
and domain name of the inverter and confirm.
-
The inverter website is displayed.
Click the "Device configuration" button.
Log in to the login area with the "Technician" user and the technician pass-
word.
Access the "Components" menu area.
Click the "Add component" button.
In the "Position" drop-down list, select the meter type (producer/load meter).
Enter the previously assigned address in the "Modbus address" input field.
Enter the name of the meter in the "Name" input field.
In the "Category" drop-down list, select the category (producer or load).
Click the "Add" button.
Click the "Save" button to save the settings.