Configuration Menu - Structure And Parameters - Fronius TS 65A-3 Operating Instructions Manual

Smart meter
Hide thumbs Also See for TS 65A-3:
Table of Contents

Advertisement

Image
*
**
Configuration
Screen
menu - structure
PASS***
and parameters
nPASS
SYStEM
MEASurE
InStALL
P int
MOdE
tArIFF
HoME
Ad-
drESS***
bAUd
PArITY
30
Scree
n
19
Displayed when easy connection mode is activated (measurement = A).
This value indicates the total energy without considering the direction.
Factory setting - displayed when drawn and delivered energy are meas-
ured separately (measurement = b).
Code
P1
Enter the current password
P2
Password change **
P3
Type of system
P6
Measurement mode **
P7
Connection check
P8
Average power calculation
interval (minutes)
P9
Display mode **
P10
Tariff management **
P11
Screen showing measured
variables displayed at star-
tup and after 120 seconds
of inactivity **
P14
Modbus address
P15
Baud rate (kBit/s) **
P16
Parity **
Description
Effective power
1.
Description
Values
2633*
Four digits (0000-9999)
3Pn*: three-phase system,
4-core
3P: three-phase system, 3-
core
2P: two-phase system, 3-
core
A: easy connection, meas-
ures all energy without tak-
ing the direction into ac-
count.
B*: measures imported and
exported energy separately.
On: activated
Off*: deactivated
1* - 30
Full*: full display
Easy: reduced display. The
values that are not dis-
played are still transmitted
via the serial interface.
On: activated
Off*: deactivated
For full display (Mode =
Full): 0 - 20*
1* - 247
9.6* / 19.2 / 38.4 / 57.6 /
115.2
Even/No*

Advertisement

Table of Contents
loading

Table of Contents