Setting the address on the Fronius Smart Meter TS Start-up Fronius SnapINverter General Connecting to the Fronius Datamanager Configuring the Fronius Smart Meter TS as the primary meter Configuring the Fronius Smart Meter TS as a secondary meter Fronius GEN24 inverter General Installation using the web browser...
Safety rules Explanation of DANGER! safety notices Indicates immediate danger. ▶ If not avoided, death or serious injury will result. WARNING! Indicates a potentially hazardous situation. ▶ If not avoided, death or serious injury may result. CAUTION! Indicates a situation where damage or injury could occur. ▶...
Any safety devices that are not fully functional must be repaired by an author- ised specialist before the device is switched on. Never bypass or disable protection devices. For the location of the safety and danger notices on the device, refer to the sec- tion headed "General remarks"...
Fronius Smart Meter TS 65A-3 Device descrip- The Fronius Smart Meter TS is a bidirectional electricity meter which optimises tion self-consumption and records the household's load curve. In conjunction with the Fronius inverter, Fronius Datamanager and Fronius data interface, the Froni- us Smart Meter TS provides a clear overview of a user's own power consumption.
Dangerous electrical voltage. Intended use The Fronius Smart Meter TS is a fixed piece of equipment for public grids of TN/TT systems and records self-consumption and/or individual loads in the sys- tem. The Fronius Smart Meter TS is required for systems with a battery storage...
Scope of supply 2x protective cover Fronius Smart Meter TS 65A-3 2x seal wire 2x connection cover Quick Start guide Positioning The Fronius Smart Meter TS can be installed in the following positions in the sys- tem: Positioning at the feed-in point:...
Page 14
Positioning at consumption point: For use as a secondary meter to measure individual loads and producers, see chapter Multi-meter system - Fronius SnapINverter on page 24.
The update can be started via the in- verter web page or using Solar.web. If several Fronius Smart Meter TS are installed in the system, set the address (see "Setting the address" under "Setting the address on the Fronius Smart...
The Fronius Smart Meter TS consumes 10 - 30 mA, the nominal capacity of the disconnecting devices and the overcurrent‑protection is determined by the wire thickness, the mains voltage and the required breaking capacity. Disconnecting devices must be mounted within sight and as close as possible to the Fronius Smart Meter TS;...
Connecting the Connect the data communication connections of the Fronius Smart Meter TS to data communic- the Modbus interface of the Fronius inverter using a network cable (type CAT5 ation cable to or higher). the inverter...
Two wires can be installed in each terminal; the wires are twisted first, inser- ted into the terminal and tightened. Note: A loose wire can disable an entire area of the network. The data communication connections of the Fronius Smart Meter TS are electrically isolated from hazardous voltages. Terminating res-...
Connecting the The terminating resistor is integrated terminating res- in the Fronius Smart Meter TS and is istor manufactured with a bridge between the M and T connections (T = termina- tion). Terminating res- Due to interference, it is recommended that terminating resistors are used as il- istors lustrated below to ensure proper functioning.
* The terminating resistor is integrated in the Fronius Smart Meter TS and is manufactured with a bridge between the M and T connections (T = termination). Mounting the Insert the connection covers into the connection cover guides and press firmly.
Primary meter Records the system's load curve and provides measurement data for energy profiling in Fronius Solar.web. The primary meter also controls the dynamic feed-in control. Secondary meter Records the load curve of individual loads (e.g. washing machine, lamps, TV, heat pump, etc.) in the consumption branch and...
Primary Secondary Ohmpilot meter meter Multi-meter sys- If several Fronius Smart Meter TS are installed, a separate address must be set tem - Fronius Setting the address on the Fronius Smart Meter TS on page 31). for each (see SnapINverter The primary meter is always assigned address 1.
Terminating resistors must be positioned individually for each channel. Modbus parti- The inputs M0 and M1 can be selected for this purpose. A maximum of 4 Modbus cipants - Fronius participants can be connected to the Modbus terminal on inputs M0 and M1. GEN24...
Secondary Ohmpilot meter meter Multi-meter sys- If several Fronius Smart Meter TS are installed, a separate address must be set tem - Fronius for each (see Setting the address on the Fronius Smart Meter TS on page 31). GEN24 inverter The primary meter is always assigned address 1.
Location of the primary meter at the feed-in point. *Terminating resistor R 120 Ohm The following must be observed in a multi-meter system: Connect the primary meter and the battery to different channels (recom- mended). The remaining Modbus participants must be distributed equally. Only assign each Modbus address once.
Page 28
Image Scree Description Total active energy drawn* Power factor (L = inductive, C = capacit- ive) Total active energy drawn* Frequency Total active energy drawn* Total reactive power Total reactive energy supplied** Total reactive power Total active energy drawn** Total apparent power Total active energy drawn* Maximum demanded power (P = Peak de- mand) that has been reached since the...
Page 29
Image Scree Description Not used Active energy drawn* Apparent power Reactive energy drawn Power factor (L = inductive, C = capacit- ive) Phase voltage Conductor voltage Current...
Image Scree Description Effective power Displayed when easy connection mode is activated (measurement = A). This value indicates the total energy without considering the direction. Factory setting - displayed when drawn and delivered energy are meas- ured separately (measurement = b). Configuration Screen Code...
Settings that need to be configured. Setting the ad- Symbol Name Event Function dress on the Scroll one screen forward, increase the Fronius Smart value by 1 Meter TS Down Scroll one screen back, decrease the value by 1 Enter Call up settings, confirm value 2 seconds Press and hold "Enter"...
The service password must be entered in order to access the "Meter" menu item. Three-phase or single-phase Fronius Smart Meter TS can be used. In both cases, the selection is made under the "Fronius Smart Meter" item. The Fronius Datamanager automatically identifies the meter type.
Click the button to save the settings. The Fronius Smart Meter TS is configured as a primary meter. The "Current general view" menu area displays the power of the PV modules, self-consumption, the energy fed into the grid and the battery charge (if avail- able).
The service password must be entered in order to access the "Device configura- tion" menu item. Three-phase or single-phase Fronius Smart Meter TS can be used. In both cases, the selection is made under the "Components" menu area. The meter type is de- termined automatically.
Access the "Components“ menu area. Click the "Add component" button. In the "Position" drop-down list, set the position of the meter (feed-in point or consumption point). For more information on the position of the Fronius Smart Meter TS, see Positioning on page 13.
Page 39
The Fronius Smart Meter TS is configured as a secondary meter.
Technical data Technical data Modbus transmission speed: 9600 baud Parity bit:none Software version: Fronius Datamanager 2.0 (from version 3.16.1 onwards) Fronius Symo Hybrid (from version 1.16.1 onwards) Measuring input Nominal voltage 208 - 400 V Operating range 166.4 - 480 V Power consumption in the voltage ≤...
0.05 mm² Recommended torque max. 0.4 Nm Fronius manu- Detailed, country-specific warranty terms are available on the internet: facturer's war- www.fronius.com/solar/warranty ranty To obtain the full warranty period for your newly installed Fronius inverter or storage system, please register at: www.solarweb.com.