Replacement Checklists
Item
Original Unit: 3G2A5-LK009
LR Area
LR 00 to LR 63
(LR 00 to LR 31 in C500)
PC Link Error
SR 247 to SR 250/SR258
and PLC Run
(SR 62 in C500)
Flags
Level Flags
Level #1
Single-
level or
level #0
PC Link Unit
Level #1
Restart Bits
Single-
level or
level #0
Checklist 7
Item
Original Unit: 3G2A5-LK009/C500-
CPU Bus
Not applicable
Unit unit
number
Node
Check setting on pins 1 to 5: [
address
Pins
1 to 5
address
00000
00001
00010
00011
00100
00101
00110
00111
01000
01001
01010
01011
01100
01101
01110
01111
Replacement Unit: C500-LK009-V1
LR 00 to LR 63
(LR 00 to LR 31 in C500)
SR 247 to SR 250/SR258
(SR 62 in C500)
AR 2411
Level #1
(Except C500)
AR 2412
Single-
level or
(Except C500)
level #0
SR 25210
Level #1
(SR 6010 in C500)
SR 25214
Single-
(SR 6014 in C500)
level or
level #0
Use the following checklist when replacing a 3G2A5-LK009 or C500-LK009-
V1 with a CVM1-LK401.
LK009-V1
]
Node
Pins
Node
1 to 5
address
0
10000
16
1
10001
17
2
10010
18
3
10011
19
4
10100
20
5
10101
21
6
10110
22
7
10111
23
8
11000
24
9
11001
25
10
11010
26
11
11011
27
12
11100
28
13
11101
29
14
11110
30
15
11111
31
AR 2411
(Except C500)
AR 2412
(Except C500)
SR 25210
(SR 6010 in C500)
SR 25214
(SR 6014 in C500)
Replacement Unit: CVM1-LK401
Any unique number in setting
range (Do not set the same unit
number on two CPU Bus Units in a
PLC.)
Set the CVM1-LK401's node
address to the same node address
that was set on the 3G2A5-LK009/
C500-LK009-V1. Set the rotary
switches in 2-digit decimal.
If upgrading from a C500 PLC, set
a node address between 00 and
07.
NODE
No.
0
0
×10
×10
1
Section 3-6
Remarks
---
Remarks
Do not mount more PC
Link Units than allowed.
Check the node address
settings on other nodes in
the PC Link to confirm
that the same address is
not already taken.
A Unit error will not occur
if the same node address
is set on two PC Link
Units in the same PC
Link, but there will be
data errors in the LR
Area.