Factory Default; Firmware Update - CEL-MAR ADA-4040PC3 User Manual

Sunmaster to modbus-rtu protocol converter
Table of Contents

Advertisement

ADA-4040PC3

5.3. FACTORY DEFAULT

In case of faulty functioning ADA-4040PC3, can be restored the factory default setting of the converter internal registers.
Set SW1 microswitch mode as in the table below.
SW1-1
SW1-2
OFF
ON
Disconnect the power and after while connect again the power. After that, will be loaded the factory default setting to the converter
internal registers.
After this operation, the converter parameters should be set again for operating in the application.
Set micro switch SW1 to run mode as shown in the table below.
SW1-1
SW1-2
OFF
OFF
In the RUN mode the yellow LED (located near the SW1), will turn off.

5.4. FIRMWARE UPDATE

Set SW1 micro switch to configuration mode as in table below.
SW1-1
SW1-2
ON
OFF
In the configuration mode the yellow LED will blink with frequency 1Hz. Press a button [Load New Firmware] to change the software
delivered by manufacturer. The Select File window will open (fig. below) and select the *.bin file then click [Open] - software will be
load to ADAConfig buffer storage and will be checked. If the ADAConfig not detect errors in loaded file, change converter software.
Process of updating is visualized by ADAConfig in use Progress Window and after proper changing confirmed by correct message.
Fig. 8. View of ADAConfig software interface
9