Troubleshooting; Configuration; Operation Mode; Configuration By Using Adaconfig - CEL-MAR ADA-4040PC3 User Manual

Sunmaster to modbus-rtu protocol converter
Table of Contents

Advertisement

ADA-4040PC3

4.2. TROUBLESHOOTING

Problem
PWR LED is not light
Rx LED lights continuously
No transmission
Tx LED is blinking

5. CONFIGURATION

5.1. OPERATION MODE

The ADA-4040PC3 converter can operates in a few modes :
RUN mode,
configuration mode,
factory default
emergency firmware update mode,
Those modes can be set by use SW1 located by terminal block RS455/RS422 (SUN). To set the switch section, should remove
terminal cover marked as SW1 and make the appropriate settings by the use a small, flat screwdriver.
All available adjusting the SW1 switch are shown in table below.
Converter operation modes
SW1- 1
SW1- 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON

5.2. CONFIGURATION BY USING ADACONFIG

The configuration of ADA-4040PC3 converter can be made by the use of ADAConfig Software - selling with converter.
To make the configuration, connect converter to computer (see pt. 3.2) and power supply. If after power, on the front panel is not lit
green LED PWR, check the power connection (polarity). If the PWR LED lights, set the section of SW1 switch to configuration mode
as in table below.
SW1-1
SW1-2
ON
OFF
In the configuration mode yellow LED located by SW1 micro-switch will blink with frequency 1 Hz. Start the ADAConfig Software and
make the configuration of transmission parameters for each converter interfaces. First, should be set the number of COM port for
communication with the converter, then readout the configuration from ADA-4040PC3 memory using the button [Read converter
configuration] and make the proper changes of each interfaces setting, as below:
– setting of the converter address from the side of RS485 MODBUS-RTU bus – in group [Converter Address] select field [Enable]
and enter address MODBUS-RTU in field [Address] (scope 1-247),
– setting of address SunMaster inverter, connected to RS485 port, field [Mapped address] (scope 1-255),
If SunMaster inverter address is known, in group [Converter Address] select field [Address mapping] and enter address of
SunMaster inverter in the field [Mapped address].
If SunMaster inverter address is unknown, in group [Converter Address] unselect field [Address mapping] and in the field [Mapped
address] don't enter any data.
– baud rate (kbps): 0.3, 0.6, 1.2, 1.8, 2.4, 4.8, 7.2, 9.6, 14.4, 19.2, 28.8, 38.4, 57.6, 76.8, 115.2, 230.4,
– number of data bites: 5, 6, 7, 8,
– control parity: no control, parity control, control of none parity,
– number of stop bits : 1, 2,
– frame spacing – range from 4 to 255 (time silence as frame's end),
After configuration, the setting should be saved on converter memory by using button [Write converter configuration].
Return to work in RUN mode is made by using SW1 switch as below.
SW1-1
SW1-2
OFF
OFF
In the RUN mode the yellow LED (located near the SW1), will turn off.
Check polarization and parameters of connected power supply.
RS485(4W) /422 network. Wrong polarization on terminals: Rx+, Rx- of RTU port; change
polarization.
RS485(4W) / RS422 network. Check correctness of connection to terminals Tx, Rx;
according to point 3 and the converter configuration.
Mode
Run
Configuration
Factory default
Emergency firmware update
Solutions
8

Advertisement

Table of Contents