ADA-4040PC6

5.3. FACTORY DEFAULT

In case of faulty functioning ADA-4040PC6, can be restored the factory default setting of the converter internal registers.
Set SW1 microswitch mode as in the table below.
SW1-1
SW1-2
OFF
ON
Disconnect the power and after while connect again the power. After that, will be loaded the factory default setting to the converter
internal registers.
After this operation, the converter parameters should be set again for operating in the application.
Set micro switch SW1 to run mode as shown in the table below.
SW1-1
SW1-2
OFF
OFF
The yellow LED (located near the SW1) will turn off in the RUN mode.

5.4. FIRMWARE UPDATE

Set SW1 micro switch to configuration mode as in table below.
SW1-1
SW1-2
ON
OFF
In the configuration mode the yellow LED will blink with frequency 1Hz. Press a button [Load New Firmware] [7] to change the
software delivered by manufacturer. The Select File window will open (fig. below) and select the *.bin file then click [Open] - software
will be load to ADAConfig buffer storage and will be checked. If the ADAConfig not detect errors in loaded file, change converter
software. Process of updating is visualized by ADAConfig in use Progress Window and after proper changing confirmed by correct
message.
During loading software the yellow LED located beside SW1 micro-switch will blink, showing data flow to the converter. If the software
was loaded correctly yellow LED will be blink with frequency 1 Hz.
After that, set microswitch SW1 to run mode as shown in the table below.
SW1-1
SW1-2
OFF
OFF
The yellow LED (located near the SW1) will turn off in the RUN mode.

5.5. EMERGENCY FIRMWARE UPDATE

In case of the unsuccessful update of the converter software, try again according to description in the above point. If the update is still
incorrect use emergency firmware update. Set SW1 microswitch mode as in the table below.
SW1-1
SW1-2
ON
ON
After microswitch setting, should be restarted ADA-4040PC6, by turning OFF and then ON the power supply. The yellow LED will light
continuously and the converter will be in Emergency Firmware Update mode. Now follow the description in the above point.
After successful software update, set microswitch SW1 to the run mode as shown in the table below.
SW1-1
SW1-2
OFF
OFF
The yellow LED (located near the SW1) will turn off in the RUN mode.

6. DATA TRANSMISSION DIAGNOSTICS

To readout diagnostics, the SW1 microswitch should be set to the configuration mode.
SW1-1
SW1-2
ON
OFF
In the configuration mode the yellow LED will blink with frequency 1Hz..