Power Supply Connection; Configuration; Operating Mode Setting; Factory Default - CEL-MAR ADA-4020 Series User Manual

Rs-485 / rs-422 to current loop converter
Table of Contents

Advertisement

ADA-4020
Using ADA-4020 converters it is possible to create Current Loop bus as above.
In above example the current loop bus creates on converter ADA-4020-1-1-2-2-3 (MASTER – Active Transmitter), one converter
ADA-4020-1-1-2-2-3 (SLAVE - Active Transmitter) furthest from the converter MASTER and max. 14 converters ADA-4020-1-1-2-2-3
(SLAVE – Passive Transmitter). The number of SLAVE converters can be less for long lines.

3.6. POWER SUPPLY CONNECTION

The power supply to the ADA-4020 converter should be DC (regulated) from 10 V= to 30V=. Nominal power is typically 2W, e.g. ZS-
12/250, DR-15-24. Power cable from DC power supplies to device must not be longer than 3m.
Observe the polarity, connect positive (+) of DC power supplies to V+ and negative (-) end to V- terminal. ADA-4020 has the protection
from opposite connection power supply. If after connection power supply on the front panel of the converter not light green LED PWR,
check correctness of power connection (polarization).

4. CONFIGURATION

The operating mode of ADA-4020 converter is set by the use of 6-positions SW1 switch.
This switch is located near the screw terminal block (see Fig.1). To set the SW1 should be removed a terminal cover and using small,
flat screwdriver make correct setting.

4.1. OPERATING MODE SETTING

All available operating modes are shows in table below.
If there are any additional questions, please contact with technical support: suppor@cel-mar.pl or on the phone: +48 41 362-12-46.
Table 1.
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6
OFF
OFF
OFF
ON
ON
ON

4.2. FACTORY DEFAULT

During production ADA-4020 converter is configured to operating in RS485 mode as in table below.
Table 2.
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5
ON
ON
ON

5. ACTIVATION

Converter can be powered after proper connection according to steps above. If the connection was made properly green LED PWR on
front panel of converter should lit, if not check polarization of power connection. If the red LED RX is lit check correctness of
connection transmitting line of Current Loop Device. The lighting of RX LED indicates no current flow through the optocoupler in the
receiver's circuit.
During proper data transmission through converter the LEDs Tx and Rx should blink.
LED
PWR
RX
TX
OFF
OFF
OFF
ON
ON
ON
SW1-6
ON
ON
ON
Signalization of Power Supply
Signalization of data receiving by ADA-4020 from Current Loop.
Signalization of data transmission from ADA-4020 converter through Current Loop
Description
RS-422 network
RS-485 network, automatic data flow
control
Description
10
Operating mode
4-wire RS422 network.
Full duplex or half duplex
transmission.
2-wire and 4-wire RS485 network.
Full duplex or half duplex
transmission.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ada-4020-1-1-1-2-3

Table of Contents