SECTION 3 - HANDLING, STORAGE, AND INSTALLATION

Figure 147 - Split Coil - Opposite Side Connections

Hot and Chilled Water Coils

1. Connect the water supply to the header connec-
tion on the leaving air side of the coil to achieve
the counter flow of water and air. The return pipe
will be connected to the remaining coil connec-
tion.
2. Install an air vent in place of the top pipe plug on
the return header. To provide for drainage, install
a drain line and shutoff valve in the supply near
the coil, or in place of the plug in the supply con-
nection as shown in Figure 148 on page 89 and
Figure 149 on page 90.
VENT
COIL
COIL

Figure 148 - Chilled Water Coil Connections Example - (Not for Construction)

Form PA102.20-N1
LD16562
PT
PLUG
RETURN
SUPPLY
DRAIN
GLOBE
UNION
VALVE
RETURN
SUPPLY
PT
GATE
PLUG
VALVE
GATE VALVE W/
HOSE BIB
89
Installation & Assembly Manual │ PACE
Water Coil Performance
Full steam pressure of water flow must
be supplied at all times - modulating
valves must not be used. A modulating
steam valve or preheat coil can actually
cause the coil to retain condensate due
to a reduced pressure in the coil thus
exposing condensate in the tubes to
freezing conditions. With modulating
steam below 5 psig (valve closure) the
steam may not be fully distributed in all
of the tubes in the coil, causing the outer
tube to cool abnormally. This will create
thermal stress that can lead to possible
"outer tube failure".
The temperature rise of the air (hot water coil) or tem-
perature fall of the air (chilled water coil) leaving the
coil is dependent on the:
• Airflow across the coil,
• Gallons of water flow through the coil, and
• Entering water temperature into the coil.
Consult the job submittal form for more information.
3 WAY CONTROL VALVE
ECCENTRIC
REDUCER
UNION
REDUCING
TEE
GLOBE
VALVE
CHILLED
WATER
RETURN
STRAINER
CHILLED
WATER
SUPPLY
LD12470
Issue Date: 07/03/2018
3