Installing Hood With Moisture Eliminators; Outdoor Air Temperature And/Or Humidity Sensors; Figure 29 - Installing Gaskets; Figure 30 - Corner Connector Hole Plug (P/N 021-19568-000) - Pace PAI Installation And Assembly Manual

Indoor and outdoor air handling units
Table of Contents

Advertisement

SECTION 3 - HANDLING, STORAGE, AND INSTALLATION

Figure 29 - Installing Gaskets

If a roof seam cap has a tab only on
one end, the end without the tab goes
above the pipe chase location.
8. Repeat this procedure for each additional section.
9. For AHUs or sections without base rails, install the
corner connector hole plugs (P/N 021-19568-000)
as shown in Figure 30 on page 33 on the bot-
tom raceway corners.
Figure 30 - Corner Connector Hole Plug (P/N 021-
19568-000)
Form PA102.20-N1
LD13778
LD116514
33
Installation & Assembly Manual │ PACE

Installing Hood with Moisture Eliminators

1. Identify the correct hood and its respective loca-
tion by looking at the label as shown in SECTION
2 - PRODUCT DESCRIPTION in this manual.
2. Correct orientation is with the tracks or bird
screens to the bottom. The mounting flanges are
pre-drilled.
3. Each hood is fitted with a factory installed bird
screen unless the moisture eliminator option is
selected.
4. Apply the Butyl tape to the pre-drilled hood flanges
and back wall angle that contact the AHU panels.
5. Use the hex head screws with the EPDM washer
provided in the fastener pack.
6. Completely cover each damper opening in the
AHU panels by its respective hood. The bottom of
the hood should extend approximately 6 in. below
the AHU panel opening.
7. Center each hood over the width of the opening.
All hoods, especially those containing barometric
dampers, MUST be installed square.
8. Seal each hood gutter to the AHU panel with the
polyurethane caulk (provided).
9. When multiple hoods are installed in a stacked
space, the hoods should be approximately 1 1/2
in. apart so that the bottom hood will extend 6 in.
below the bottom of the opening.
10. If equipped, install the optional moisture elimina-
tors as shown in Figure 68 on page <?> using
the following instructions.
a. Remove the clip(s) from the leading edge of
the hood.
b. Insert the proper size moisture eliminator or
filter into the tracks.
c. Reinstall the clip(s) on the leading edge of
the hood.
Outdoor Air Temperature and/or Humidity
Sensors
When outside air hoods are shipped loose with AHUs
that include factory packaged controls, these sensors
will be dismounted and pulled back into the AHU. The
contractor should find them secured with tape inside,
and put them through their respective penetration to
the exterior, and mount them to the bracket provided.
3
Issue Date: 07/03/2018

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pao

Table of Contents