Installing Damper Actuator; Figure 49 - Installing The Direct Coupled Actuator - Pace PAI Installation And Assembly Manual

Indoor and outdoor air handling units
Table of Contents

Advertisement

SECTION 3 - HANDLING, STORAGE, AND INSTALLATION

Installing Damper Actuator

Use the following instructions to install the actuator as
shown in Figure 49 on page 41.
Damper Blade Orientation
Return air and mixing dampers
Position blades so that they will be open once the actu-
ator is installed. This will be the dampers spring return
position. Note whether the damper shaft is rotated fully
clockwise or counter clockwise.
Outside air and exhaust air dampers
Position the damper blades so that they will be closed
once the actuator is installed. This will be the dampers
spring return position. Note whether the damper shaft
is rotated fully clock-wise or counter clockwise.
Actuator Installation
1. Remove the bearing plate from the damper frame
and jackshaft.
2. Slide the damper actuator onto the open end of
this shaft making sure that the proper spring re-
turn position on the face of the actuator matches
the damper shafts rotation, if not then reinstall the
actuator with it flipped over.
PACE PART
VENDOR
NUMBER
025-25737-001
Belimo
025-25737-002
025-39114-001
025-39114-002
025-39115-001
025-39115-002
JCI
025-39116-001
025-39116-002
025-39117-001
025-39117-002
ITEM
DESCRIPTION
1
Damper
2
Actuator
3
Actuator Mounting Bracket
7.8" length, 0.25" hole,
4
black 6.6 nylon
5
Edge Clip # MCMS12-P-C
6
Cable Tie 7.9: LG

Figure 49 - Installing the Direct Coupled Actuator

Form PA102.20-N1
BRACKET
PART NUMBER
086-00138-014
086-00138-014
086-00138-013
086-00138-013
086-00138-016
086-00138-016
086-00138-014
086-00138-014
086-00138-014
086-00138-014
PACE PART NUMBER
See Spec Sht for P/N
See Spec Sht for P/N
See Table
025-40605-001
025-39067-002
025-39031-002
3. Reinstall the bearing plate to the damper frame
and jackshaft.
4. Slide the damper actuator, mounting bracket into
the actuator mounting grooves and fasten to the
damper frame using self drilling screws.
5. Securely tighten the actuator shaft clamp to the
dampers jackshaft. Make sure at this point the
damper shaft is completely rotated to its proper
position.
6. Manually operate the actuator to its fully actuated
position using the crank arm provided with the ac-
tuator then release the spring to allow the damper
to go back to its original position. This will verify
the actuators spring rotation and stroke.
7. Set the damper actuators rotation selector switch
to the proper rotation required to actuate the
damper.
This will always be opposite the spring
return rotation.
41