Installing A Single Headered (Sh) Filter; Installing A 2 In. Pre-Filter Combined With A Sh Final Filter; Figure 77 - Correctly Installed Cartridge Filter; Figure 78 - Correctly Installed Latch Pin (P/N 026-35788-604) - Pace PAI Installation And Assembly Manual

Indoor and outdoor air handling units
Table of Contents

Advertisement

PACE │ Installation & Assembly Manual

Installing a Single Headered (SH) Filter

Use the following instructions to install a 2 in. Single
Headered (SH) filter into a 16 g galvanized hold-
ing frame with four latches (P/N 026-24788-702), as
shown in Figure 72 on page 48.
1. Install one latch at each corner (4 corners) of the
frame. The latch fits into two rows of three knock-
outs. Use the row of knockouts closest to the gas-
ket for nominal 1 in. filters or filters with a 13/16 in.
single header. Use the second set of knockouts
for nominal 2 in. filters
2. Insert the straight end of the latch between the
two knockouts furthest from the corner.
3. Using a moderate amount of pressure, force the
latch over the third knockout. The latch should
now be trapped within the three knockouts, but
should be able to freely rotate.
4. The latch installation should be complete.
5. Rotate the latches outward, and insert the SH filter
into the frame. Insert the bulk of the filter through
the frame, protruding out the backside. Only the
header of the filter should be contacting the flange
of the frame.
6. After the filter is placed into the frame, grasp the
circular end of the latch and rotate it across the
corner of the filter.
7. Push the end of the latch towards the filter, until
the latch catches beneath the frame knockout.
8. Repeat the process with the remaining latches.
9. The filter should now be securely installed into the
frame as shown in as shown in .

Figure 77 - Correctly Installed Cartridge Filter

Issue Date: 07/03/2018
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
Installing a 2 in. Pre-Filter Combined with
a SH Final Filter
Use the following instructions to install a 2 in. pre-filter
combined with a SH final filter (Multi-Cell FM Single
Header or Multi-Sak) into a 16 g galvanized hold-
ing frame with four latches (P/N 026-35778-604), as
shown in Figure 72 on page 48.
1. Follow the instructions for the SH filters on the
previous page, and then proceed with the follow-
ing instructions for 2 in. pre-filters.
2. Insert the straight end of the latch between the
two knockouts furthest from the corner.
3. Using a moderate amount of pressure, force the
latch over the third knockout as shown in Figure
78 on page 52.
Figure 78 - Correctly Installed Latch Pin (P/N 026-
35788-604)
4. Grasp the loose end of the latch, and place it over
the pre-filter frame, so that the latch secures the
pre-filter to the SH filter.
5. Repeat the process with the remaining latches.
6. The filters should now be securely installed into
the frame as shown in Figure 79 on page 52.
LD10148

Figure 79 - Correctly Installed Cartridge with Pleats

52
LD10496
LD10160
Form PA102.20-N1