Engineering Data; Derating Curve - Omron S8VK-C Manual

Switch mode power supply
Table of Contents

Advertisement

Available languages

Available languages

Engineering Data

Derating Curve

120 W (S8VK-T12024)
120
100
80
60
40
20
0
−40
−25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
Note:
This is the guaranteed value for startup. (3-phase only)
A. Standard mounting
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
240 W (S8VK-T24024)
120
100
80
60
40
20
0
−40
−25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
Note:
This is the guaranteed value for startup. (3-phase only)
A. Standard mounting
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
480 W (S8VK-T48024)
120
100
80
60
40
20
0
−40
−25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
Note:
This is the guaranteed value for startup. (3-phase only)
A. Standard mounting
Over 528 VAC: the derating is 0.21%/VAC
Over 746 VAC: the derating is 0.16%/VDC
B. Face-up mounting at 480 VAC or lower or 678 VDC or lower
C. Face-up mounting at 576 VAC or lower or 810 VDC or lower
960 W (S8VK-T96024): Standard mounting
A
B
C
Note:
A
B
960 W (S8VK-T96024): Face-up mounting
C
Note:
A
B
C
120
100
80
60
40
20
0
−40
−25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
This is the guaranteed value for startup. (3-phase only)
A. 3-Phase (340 VAC or over to 576 VAC or lower)
For less than 340 VAC, it is possible to use with output voltage at
28.5 VDC or lower and load rate 60% or lower.
B. 2-Phase (380 VAC or over to 576 VAC or lower, and output voltage
26.4 VDC or lower)
C. 2-Phase (360 VAC or over to 380 VAC or lower, and output voltage
26.4 VDC or lower)
For 340 VAC or over to less than 360 VAC, it is possible to use with
output voltage at 26.4 VDC or lower, and whichever is the smaller of
the load rate 60% or lower or the value of C.
120
100
80
60
40
20
0
−40
−25 −10 0 10 20 30 40 50 60 70 80
Ambient temperature (°C)
This is the guaranteed value for startup. (3-phase only)
D. 3-Phase (340 VAC or over to 576 VAC or lower)
For less than 340 VAC, it is possible to use with output voltage at
28.5 VDC or lower and load rate 60% or lower.
E. 2-Phase ( 380 VAC or over to 480 VAC or lower, and output voltage
26.4 VDC or lower)
F. 2-Phase (Over 480 VAC to 576 VAC or lower)
For 340 VAC or over to less than 380 VAC, it is possible to use with
output voltage at 26.4 VDC or lower, and whichever is the smaller of
the load rate 60% or lower or the value of F.
S8VK-T
B
C
A
D
E
F
7