Application Examples; Protecting A Circuit-Breaker Controlled Motor - ABB REM 610 Technical Reference Manual

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 755537
5.2.
5.2.1.
Motor protection Relay
Technical Reference Manual

Application examples

Protecting a circuit-breaker controlled motor

Data of the squirrel cage motor stated by the manufacturer:
Rated power, P
nm
Rated voltage, U
nm
Rated current, I
nm
Start-up current of the motor
Start-up time of the motor
Safe stall time
Ambient temperature
CT current ratio
Setting calculations
The FLA secondary scaling factor is calculated as follows:
1000A
5A
×
1.075
--------------- -
------ -
=
930A
5A
For a direct-on-line started motor, p = 50%.
At an ambient temperature of 40°C the internal FLA equals the FLA of the motor.
Thus the start-up current of the motor is 6.2 x the internal FLA.
The safe stall time setting, t
load 1 x FLA. A safe stall time setting of 30 seconds is selected, permitting a
start-up time slightly longer than the one stated by the motor manufacturer.
By selecting the correct trip curve from the trip curves at no prior load according to
the previously selected or calculated safe stall time setting, the total start-up time of
the motor can be read from the curve. In this case, the thermal protection element
will trip in approximately 28 seconds, which will allow two cold starts.
However, as the operate time when no prior load is longer than the safe stall time of
nineteen seconds, single motor start ups should instead be protected by the start-up
supervision. The start-up current, 48/14 PICKUP, is set to equal the start-up current
of the motor and the start-up time, 48/14 TDLY, to approximately ten per cent above
the start-up time of the motor in order to leave a safety margin for operation. Thus
48/14 TDLY is set to 1 s x 1.1
As the safe stall time is longer than the start-up time of the motor, no speed switch
will be required.
As one motor start up uses 11 s/28 s
restart disable level, 49 REDIS, should be set to below 61 per cent, e.g. to 55 per
cent.
The prior alarm level, 49 ALARM, is set to 80...90 per cent of the trip level.
The time constant multiplier, K
4500 kW
3300 V
930 A
6.2 x FLA
11 s
19 s
40°C
1000/5 A (relay input = 5 A)
1.08
, is calculated or selected from the trip curves at prior
6x
12 s.
39% of the thermal capacity of the motor, the
, is set to 4.
c
REM 610
125

Advertisement

Table of Contents
loading

Table of Contents